PL2200C
Technical specifications |
Type
Output
[kW]
PL2210CA
0
PL2215CA
0
PL2220CA
0
Technical specifications |
Type
Output
step
[kW]
PL2210CE05
3,3/5
4/8
PL2215CE08
PL2220CE10
5/10
Technical specifications |
Type
Output*
3
[kW]
PL2210CW
6,9
PL2215CW
11,1
PL2220CW
14,4
*
) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m². At lowest/highest airflow.
1
) ∆t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*
2
*
) Applicable at water temperature 80/60 °C, air temperature, in +18 °C.
3
Protection class for units with electrical heating: IP20.
Protection class for units without heating and units with water heating: IP21.
CE compliant.
Type
C1 Mid
[mF]
PL2210CE05
6
PL2215CE08
8
PL2220CE10
6
7
PL2210CW
8
PL2215CW
PL2220CW
7
PL2210CA
6
PL2215CA
8
PL2220CA
6
14
PL2200C A without heat
Airflow
[m
/h]
3
900/1200
1150/1800
1800/2400
PL2200C E with electrical heat
∆t
Airflow
*2
[m
/h]
[°C]
3
900/1200
17/12,5
1150/1800
21/13
1800/2400
17/12,5
PL2200C W with water heat
∆t
Airflow
*2,3
[m
/h]
[°C]
3
700/1200
21/17
1000/1750
23/18
1400/2400
22/18
C2 Low
C2 Run
[mF]
[mF]
5
3
6
4
5
3
5
3
6
4
5
3
5
3
6
4
5
3
1
Sound
Voltage
level*
motor
1
[dB(A)]
[V]
42/51
230V~
40/52
230V~
43/53
230V~
3
Sound
Voltage
level*
motor
1
[dB(A)]
[V]
42/51
230V~
40/52
230V~
43/53
230V~
2
Water
Sound
volume
level*
1
[l]
[dB(A)]
0,38
39/52
0,81
37/53
0,74
40/53
Amperage
Length
motor
[A]
[mm]
0,45
1026
0,5
1536
0,9
2026
Amperage
Voltage [V]
motor
Amperage [A]
[A]
(heat)
0,45
400V3~/7,2
0,5
400V3~/11,5
0,9
400V3~/14,4
Voltage
Amperage
Length
motor
motor
[V]
[A]
[mm]
230V~
0,4
1026
230V~
0,5
1536
230V~
0,8
2026
Weight
[kg]
16
24
32
Length
Weight
[mm]
[kg]
1026
17
1536
26
2026
34
Weight
[kg]
17
26
35