Télécharger Imprimer la page

Greengate LiteKeeper 8 LK8-NO Instructions D'installation page 5

Publicité

Les langues disponibles

Les langues disponibles

6.
To program the controller to control a Two Pole Relay
Module, apply programming to the relay number where
the relay pin connector is attached to the MRC.
Wiring Terminal
Block
Line 1
Load 1
Line 2
Load 1
Relay Slot Pin Connector:
Please note relay number
location for programming
purposes.
Two Pole Relay Module
Two Pole Relay Module Wiring
1.
Connect one de-energized branch circuit breaker to one
of the relay terminal blocks
2.
Connect the load side to the output terminal block
position of this same terminal block. Note: terminal
blocks are not polarity sensitive although it is
recommended that line and load be brought into
terminal blocks in the same manner for consistency.
3.
Connect the other de-energized branch circuit breaker
to the other relay terminal block on the module.
4.
Connect the second load wire to the second
terminal block.
5.
Tighten down relay terminal screws. Manufacturer's
recommended torque rating is 18lbs-in.
(1.475 foot-lbs) (2.0 Nm).
6.
Document relay to circuit information for
future reference.
Two Pole Relay Card Notes
The Two Pole Relay Card(s) is installed at the factory in the
Lighting Controller specified.
The Two Pole Relay Card relays are shipped separately and
are installed in the field. The relays that are available are
Two Pole Relays rated at 120V/208V or 277V/480V. A Single
Pole Relay is also available, rated at 347V. All relays are
rated to 20 Amps. The following information describes the
installation of the relays onto the Two Pole Relay Card.
LittKttptr® 8
Relay Status
Indicator LED
TPRM
Each Two Pole Relay Card has eight mounting clips for the
placement of the relays. The Two Pole Relay Card will hold
eight 208V two pole relays, one in each mounting clip. The
480V Two Pole Relay Card uses two mounting clips, thus
only four relays will fit per card. The Two Pole Relay Card
will hold eight 347 Single Pole Relays, one in each mounting
clip.
1.
Position the relay so that the input coil faces the center
of the Two Pole Relay Card and the output contacts
face outwards toward the enclosure walls.
2.
Place the input coil side in first then press down with
an even motion and snap the relay into place. (To
remove the relay, press down on the metal release bar
and pull the relay out).
3.
The coil control wires (blue and red) and a connector
are supplied already attached to the relay. Simply plug
this connector into the Two Pole Relay Card. The relay
number slot that this connector is plugged into will
be the relay that will need to be programmed in the
controller for proper function. Wire as indicated in the
diagram following.
Two Pole Relay Card
with Four 208V Two Pole Relays.
Two Pole Relay Card
with Four 347V Single Pole Relays
Two Pole Relay Card
with Two 480V Two Pole Relays
Two Pole Relay Card Wiring
Connecting Relay Loads
Mounting Clip
Output Contact
Terminals
Load 2 (Out)
Line 2 (In)
Line 1 (In)
Load 1 (Out)
Input Coil with Connector
Mounting Clip
Output Contact
Terminals
Load 2 (Out)
Line 1 (In)
Input Coil with Connector
Mounting Clip
Output Contact
Terminals
Line 1 (In)
Load 1 (Out)
Line 2 (In)
Load 2 (Out)
Input Coil with Connector