Running time
Slat change-over time
Fabric-stretching time
Minimum change-over-time
Invert movement direction
Behaviour on voltage return
Configured venetian blind po-
sition
Configured slat position
Behaviour after the end of the
disabling function
Manual saving of the scene
values
Priority, lock-out protection
Activate lock-out protection
blind position
82581443
J0082581443
1 ... 600 sec
Basic setting: 120 s
0 ms ... 10 sec
300 ms ... 10 s
Basic setting: 0 ms / 300 ms
300 ms ... 10 sec
Basic setting: 1 s
On, Off
Basic setting: Off
No change
Configured value
Basic setting: No change
0 ... 100 %
Basic setting: 0 %
0 ... 100 %
Basic setting: 0 %
no change
Last value
Down
up
Basic setting: No change
On, Off
Basic setting: On
0...4
Basic setting: 1
0 ... 100 %
Basic setting: 0 %
8/11
Absolute time which the
blind/shutter requires from the
top to the bottom end position.
The entry is essential if scene
or position movements are to
occur.
Absolute time for changing-
over Venetian blind slats. The
fabric stretching time can also
be set here for the Awning
operating mode.
Minimum interruption time
when changing directions. In-
creasing the minimum
change-over time will cause
less wear on the motors.
Inverts the activation of the re-
lay outputs. During inverted
operation, the relay outputs
"Up" and "Down" should be
activated in reverse. This is re-
quired, for example, for
controlling skylights.
Defines the behaviour of the
output after voltage return.
RMD design: Bus voltage re-
turn
If the value "Configured posi-
tion" is entered for the para-
meter "Behaviour after voltage
return", then the blind/shutter
position set here is approa-
ched.
If the value "Configured posi-
tion" is entered for the para-
meter "Behaviour after voltage
return", then the slat position
set here is approached.
Behaviour of the output when
a block is removed.
Disables the saving of the cur-
rent Venetian blind position as
scene value in an actuator for
a command via a transmitter.
Specifies the priority for recal-
ling and removing a scene of
type Lock-out protection for
the channel.
Defines the behaviour of the
output on activating the lock-
out protection.