IR EH Serie Manuel De L'opérateur page 13

Table des Matières

Publicité

HEATER TEMP
SET
Pressing the SET button permits the value of the HEATER
TEMPERATURE SETPOINT to be changed
HEATER TEMP
3
Use the numbers on the keypad to enter the desired value
for the HEATER TEMPERATURE setpoint.
HEATER TEMP
8
Use the numbers on the keypad to enter the desired value
for the HEATER TEMPERATURE setpoint.
HEATER TEMP
0
Use the numbers on the keypad to enter the desired value
for the HEATER TEMPERATURE setpoint.
HEATER TEMP
ENTER
Depressing ENTER saves the selected set point.
9.4 ENERGY MANAGEMENT SYSTEM (OPTIONAL)
The Energy Management System option includes a dew point sensor
that transmits the outlet pressure dew point to the Microprocessor
Controller. The Microprocessor Controller displays the outlet pressure
dew point in real-time. This option package also includes Energy
Management System, an energy savings feature that matches moisture
loading and regeneration energy usage. Drying equipment is typically
operated below full flow rating and/or below maximum water loading
capacity of the desiccant bed. The Energy Management System feature
utilizes the data communicated from the dew point sensor and extends
the normal timed switching sequence in proportion to the moisture
loading on the dryer.
When the Energy Management System feature is turned off, all
switching sequences occur as described in Section 7.3. When the
Energy Management System feature is activated, the drying sequence
is governed by the outlet pressure dew point as measured by the dew
point sensor. When the sampled outlet dew point registers below the
customer set point (-43°F default for -40°F dryers; -102°F on -100°F
dryers), an immediate change in dryer operation will not be noticeable.
The dryer will continue its normal regeneration process through tower
re-pressurization. Once the tower is re-pressurized, both towers will be
at line pressure but air will only flow through the tower indicated by the
status panel. Tower switch over sequence is delayed until the dew point
elevates above the Energy Management System setpoint, at which point
tower switch over will occur.
9.0 TECHNICIAN MODE
___
3__
38_
380
380
EH Series Desiccant Dryer Models 150-8000
http://www.ingersollrandproducts.com
NOTICE
New desiccant has a moisture holding capacity higher than the dryer's
design regeneration capacity. The desiccant ages in a three- to six-
month time period at which point it stabilizes to an "aged" state. During
this aging process at initial start-up or after desiccant replacement, the
Energy Management System feature should be deactivated.
9.4.1
ENABLING / DISABLING ENERGY MANAGEMENT
SYSTEM
The following illustrates the method of accessing and
adjusting the Energy Management System feature:
SELECT
DISPLAY
Depress the SELECT DISPLAY button until the ENERGY
MANAGEMENT SYSTEM screen is displayed.
+
-
Depress the +/- button until the desired set point is displayed.
Pressing SELECT DISPLAY saves the current selection.
9.4.2
SETPOINT ADJUSTMENT
On dryers equipped with the optional Energy Management
System the setpoint can be adjusted to match the dryers
operation to the desired pressure dew point.
The following illustrates the method of adjusting the setpoint
for the Energy Management System feature:
EMS SET POINT
SELECT
DISPLAY
Depress the SELECT DISPLAY button until the EMS SET
POINT screen is displayed.
EMS SET POINT
SET
Pressing the SET button permits the value of the EMS
SETPOINT to be changed
EMS SET POINT
+
-
To enter a negative number, depress the +/- button.
Otherwise, proceed to the next step.
EMS SET POINT
4
Use the numbers on the keypad to enter the desired
pressure dew point temperature for the EMS setpoint.
EMS: OFF
EMS: ON
-43
___
-___
-4__
11

Publicité

Table des Matières
loading

Table des Matières