4

CODE No. (DN) setting

 Wired remote controller (RBC-A S 5 )
Perform the advanced settings for the air conditioner.
Carry out the setting operation while the indoor unit is stopped. (Turn off the air conditioning unit before starting the
setting operation.)
Display example of
RBC-AMSU51-ES
1
Push the [
MENU] button to display the menu screen.
2
Push and hold the [
MENU] button and the [
setting menu".
Push and hold the buttons for more than 4 seconds.
DN setting
Indoor unit
Code (DN) I.DN
Outdoor unit
Code (DN) O.DN
Return
DN setting
Code
(DN) I.DN
Data
00B5
0000
Return
Fix
<
5-English
Field setting menu(2/2)
6.Setting timer operation mode
7.DN setting
8.Reset power consumption data
9.Notice history
Return
Set
] button at the same time to display the "Field
Set
DN setting
Code
(DN) I.DN
Data
00B5
0001
Return
Fix
>
<
>
– 3 –
3
Push the [
] / [
] button to select "7. DN setting" on the "Field setting menu" screen, then
push the "
Set" [
F2] button.
Set
Push the [
] / [
] button to select the "Indoor unit" and push the "
button.
The fan and louver of the indoor unit operate. When the group control is used, the fan and louver of the
selected indoor unit operate.
Move the cursor to select "DN code" with the "
[
] / [
] button.
Move the cursor to select "data" with the "
[
] button.
4
Push the [
MENU] button to set the other DN codes. After "Continue?" is displayed on the screen.
5
Push the "
No" [
F2] button to finish the setting operation. " " appears on the screen for a
No
while, then the screen returns to the "Field setting menu" screen.
Pushing the "
No" [
No
used. Push the [
CANCEL] button on the unit selection screen to finish the setting operation. " "
appears on the screen for a while, then the screen returns to the "Field setting menu" screen.
6
Push the [
CANCEL] button to return.
About the Occupancy sensor
• Sometimes the sensor may not detect people even when they are present if their movements are small.
• If something having a difference in temperature with the surroundings moves, the sensor may detect people as
present even if they are not present.
• A wired remote controller (RBC-A S 5 ) is required to use an occupancy sensor.
• Be sure to install an occupancy sensor in all indoor units if using group operation.
CAUTION
Wireless remote controller kit cannot be used together with the Occupancy sensor.
<" [
F1] button, then set "00B5" with the
<
>" [
F2] button, then set "0001" with the [
>
DN setting
Continue?
Return
Yes
No
F2] button displays the unit selection screen when the group control is
.
Set" [
F2]
Set
] /
6-English