INSTALLATION PROCEDURES
Step 1.
Insert the 4 "AAA" batteries into the battery compartment taking care that the connection
respects correct polarity showing on the battery holder.
Step 2.
While the 4 batteries are inserted, the Smoke Detector will sound 2 short beeps, LED start
flashing and begin the 6-minute warming period.
Step 3.
During the 6-minute warming period, you can learn the Smoke Detector into the Panel.
To do the learning process:
a) Put the Control Panel into "Add Device" Mode (or "learning" mode) to learn the ID code of
the Smoke Detector. (Please refer to operation manual of the panel.)
b) Press the Test Button on the Smoke Detector, the LED will be on for 2 sec and the buzzer
will sound a 2-tone beep to indicate it's functioning normally with successfully radio
transmitting.
c) If the Control Panel successfully receives the signal, the panel will respond accordingly to
indicate the completion of the learning-in process. Please refer to the manual of the panel.
Step 4.
When the 6-minute warming period is over, one short beep will sound to indicate that the
Smoke Detector is starting calibration process. The process will be repeated every 100 sec
and notified by a short beep respectively. The completion of calibration process will be
notified by a 2-tone beep and the LED will be turned off.
Normally it takes about 2 ~ 16 minutes to do the calibration. However, after 16 minutes, if the
Smoke Detector gives out continuous beeps instead, it indicates that the Smoke Detector is
failed in the calibration and its battery should be removed to silence the beeps. Then, start
from step 1 to try again after a pause of at least 30 seconds.
Note:
During the calibration period, pressing the Test Button is prohibited. If you are not able to do
the learning process (Step 3) during the 6-minute warming period, you are requested to do the
learning process after the calibration period (Step 4).
Step 5.
After the completion of the warming and calibration process, put the Control Panel into "Walk
Test" mode. Then, decide upon a suitable location for the Smoke Detector's installation and
from there, press the Test button to confirm this location is within signal range of the Control
Panel.
Step 6.
Using the bracket as a template, drill two holes in the exact location, the
device is to be mounted and insert the dowels.
Step 7.
Screw the bracket on with the two hooks facing down by using the screws
and screwing them into the dowels.
Step 8.
Locate the single line mark on the detector and line it up with one of the
hook of the bracket. After both hooks fits in the two mounting holes on the
detector, rotate the detector counter-clockwise to lock it in onto the
bracket. The installation is now completed.
TESTING THE SMOKE DETECTOR
By pressing the Test button on the Smoke Detector, you can test if the Smoke Detector is functioning
normally.
If the Smoke Detector functions normally, the LED will be on for 2 sec. then it will sound a 2-tone
beep.
If the buzzer sounds 3 beeps, that means the "Optical Chamber" on the Smoke Detector is
either dirty or out-of-order.
If the LED doesn't light and no beep is sounded, it means the Smoke Detector is out-of-order.
SUPERVISORY SIGNAL
After installation, the Smoke Detector will automatically transmit Supervisory Signals periodically
to the Control Panel at intervals of 60 min. to 100 min. randomly.
If the Control Panel has not received the signal from the Smoke Detector for a preset period of
time, the Control Panel will indicate it on its display to show that particular Smoke Detector is
experiencing an out-of-signal problem.