12. Neither disassemble nor modify the appliance.
13. Repairing the appliance by yourself is extremely dangerous.

0.3 - INTENDED USE

• An improper use of the appliance with possible damages caused to people,
property or animals relieves OLIMPIA SPLENDID from any liability.
For connection of the control signals, use a screened cable with minimum sec-
tion of the wires of 0.5mm
Screening MUST be connected safely to the frame of the fan coil.

0.4 - LOCKED FAN FUNCTION

a. When the printed circuit board receives from the fan motor an incorrect speed feedback (motor not
connected, locked, broken, etc.), the green led starts blinking 6 times after 5 seconds and the speed
signal to the motor is set to minimum speed.
b. After 20 seconds of operation of the fan motor, the circuit board tries again to check the feedback
received from the motor for 10 seconds.
c. If the error persists for 5 consecutive times, the motor is switched off and the green led starts blinking
2 times.
To restore the system, the circuit board must be switched off and on again.

0.5 - CONFIGURATION OF THE BOARD

Disconnect power feeding from the board before configuring the selectors
SW1.
J1 - MOUNT
ON: Wall/roof installation of the unit.
OFF: Console/floor installation of the unit
J2 - SEL1 and J3 - SEL2
SEL1
OFF
OFF
ON
ON
Only at first start-up of the board, for approximately 3 seconds, the relay of the valve carries out a
series of commutations to confirm the selected configuration.
EN - 4
FOR ALL DIAGRAMS
and maximum length of 20 metres.
2
SEL2
OFF
Units without Flap (200-1000)
ON
All versions (1400-1600)
OFF
Units with Flap (200-1000)
ON
** Reserved