REPORT NO.
5041 (MAY. 89)
• INSTALL AND USE IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION AND OPERATING INSTRUCTIONS.
• CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS, INSTALLATION PERMIT AND INSPECTION IN
YOUR AREA.
• DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE (USA. ONLY).
• USE 6 INCH / 150MM DIAMETER MINIMUM 24 MSG BLACK OR LISTED CONNECTOR.
• CONNECT TO A LINED MASONRY CHIMNEY SUITABLE FOR USE WITH SOLID FUELS.
• DO NOT OBSTRUCT THE SPACE BENEATH THE HEATER.
• SEE LOCAL BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS FOR PRECAUTIONS REQUIRED WHEN
PASSING A CHIMNEY THROUGH A COMBUSTIBLE WALL OR CEILING.
• DO NOT PASS A CHIMNEY CONNECTOR THROUGH A COMBUSTIBLE WALL OR CEILING.
• MINIMUM CLEARANCE BETWEEN SINGLE WALL CHIMNEY CONNECTOR AND COMBUSTIBLE MATERIALS-18INCHES/
455MM. CLEARANCE MAY BE REDUCED BY THE USE OF LISTED PIPE SHIELDS, WALL PROTECTORS OR OTHER
MEANS APPROVED BY LOCAL BUILDING OR FIRE OFFICIALS.
A. SIDEWALL TO UNIT
B. BACKWALL TO UNIT
C. CORNER TO UNIT
D. SIDEWALL TO CONNECTOR
E. BACKWALL TO CONNECTOR 19 in. / 485 mm
F. CORNER TO CONNECTOR
HORIZONTAL CONNECTOR NOT PERMITTED IN MOBILE HOMES
AS TESTED - PIPE SHIELD MAY BE REQUIRED BY LOCAL AUTHORITIES.
* COMBUSTIBLE ALCOVE SIZE : DEPTH - 4 FT. / 1.22 M MAXIMUM, HEIGHT 7 1/2 FT. / 2.3 M MINIMUM
COMBUSTIBLE FLOOR MUST BE PROTECTED BY A CONTINUOUS NON-COMBUSTIBLE MATERIAL EXTENDED TO THE
FRONT, SIDES AND BACK AS INDICATED.
IN CANADA
IN U.S.A.
COMPONENTS REQUIRED FOR MOBILE HOME AND ALCOVE INSTALLATION: OUTSIDE AIR KIT, AND ONE OF THE
FOLLOWING LISTED CONNECTORS: SECURITY MODELS DP OR DC, OLIVER MACLEOD MODEL PV, ENERGY VENT
E VENT, SELKIRK METALBESTOS MODEL DS, METAL FAB MODEL DW, AMERI-TEC MODEL DBSP, OR INDUSTRIAL
CHIMNEY MODEL EXCEL ULTRA-BLACK IN COMBINATION WITH ONE OF THE FOLLOWING COMPATIBLE CHIMNEY
SYSTEMS: APPLIANCE MUST BE INSTALLED WITH PEDESTAL OR LEG KIT ATTACHED.
IN CANADA - SECURITY MODEL S2100, OLIVER MACLEOD PROJET MODEL HT 3000, SELKIRK SENTINEL MODEL
CF, INDUSTRIAL CHIMNEY MODEL EXCEL 2100.
IN USA - SECURITY MODEL ASHT OR S2100, OLIVER MACLEOD MODEL 3103 OR HT 3000, SELKIRK METALBESTOS
MODEL SS II, METAL FAB MODEL 2100, AMERI-TEC MODEL HS, INDUSTRIAL CHIMNEY MODEL EXCEL 103HT.
USE COMPONENTS SPECIFIED IN PACIFIC ENERGY INSTALLATION INSTRUCTIONS.
OPTIONAL COMPONENTS - WATER COIL (CANADA ONLY), FAN KIT #SSER.BLOW, FAN ELECTRICAL RATING: 115V,
60HZ, 80WATTS. DO NOT ROUTE POWER CORD BENEATH HEATER.
CAUTION: RISK OF EXCESSIVE TEMPERATURES - KEEP ASH DUMP CLOSED DURING FIRING OF THE HEATER.
OPERATE ONLY WITH FEED DOOR CLOSED. OPEN TO FEED FIRE ONLY.
KEEP FURNISHINGS AND OTHER COMBUSTIBLE MATERIALS WELL AWAY FROM HEATER.
REPLACE GLASS ONLY WITH CERAMIC GLASS.
U.S. ENVIRONMENTAL PROTECTION
AGENCY CERTIFIED TO COMPLY WITH
JULY, 1990, PARTICULATE EMISSION
STANDARDS
080100
CERTIFIED FOR CANADA AND U.S.A.
LISTED ROOM HEATER, SOLID FUEL TYPE.
ALSO FOR USE IN MOBILE HOMES
TESTED TO CAN/ULC S627-M90 AND UL 1482-88
SUPER 27
MODEL SERIES D:
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
RESIDENTIAL INSTALLATION
USING SINGLE WALL CONNECTOR
VERTICAL CONNECTOR HORIZONTAL CONNECTOR
18 in. / 455 mm
14 in. / 355 mm
12 in. / 305 mm
8 in. / 200 mm
11 in. / 280 mm
11 in. / 280 mm
27 in. / 685 mm
23 in. / 585 mm
15 in. / 380 mm
22 in. / 560 mm
22 in. / 560 mm
BACK I
G.
18 INCHES / 455 MM
H
H.
8 INCHES / 200 MM
I.
8 INCHES / 200 MM
G.
16 INCHES / 405 MM
H.
5 INCHES / 127 MM
I.
0 INCHES / 0 MM
CAUTION
HOT WHILE IN OPERATION. DO NOT TOUCH. KEEP CHILDREN,
CLOTHING AND FURNITURE AWAY. CONTACT MAY CAUSE SKIN
BURNS. SEE NAMEPLATE AND INSTRUCTIONS.
MADE IN CANADA
5050.75
WH-
WH-
SPECTRUM
RESIDENTIAL CLOSE CLEARANCE
INSTALLATION
USING DOUBLE WALL CONNECTOR
VERTICAL CONNECTOR HORIZONTAL CONNECTOR
14 in. / 355 mm
14 in. / 405 mm
5 in. / 127 mm
5 in. / 127 mm
4 in. / 102 mm
4 in. / 102 mm
22.5 in. / 570 mm 22.5 in. / 570 mm 24.5 in. / 620 mm 24.5 in. / 620 mm
11.5 in. / 292 mm 11.5 in. / 292 mm 16.5 in. / 420 mm 14.5 in. / 370 mm
14.5 in. / 370 mm 14.5 in. / 370 mm
BACK WALL
B
E
H
A
HEATER
D
G
FRONT
PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
PO. BOX 1060, DUNCAN, BC V9L 3Y2
DATE OF MANUFACTURE
J
F
M
A
M J
1999
2000
2001
DO NOT REMOVE THIS LABEL
CLASSIC
* ALCOVE
MOBILE HOME
INSTALLATION
INSTALLATION
USING
USING
DOUBLE WALL
DOUBLE WALL
CONNECTOR
CONNECTOR
16 in. / 405 mm
16 in. / 405 mm
10 in. / 255 mm
8 in. / 200 mm
N/A
8 in. / 200 mm
N/A 18.5 in. / 470 mm
ADJACENT WALL
C
F
MANUFACTURED BY:
J
A S O N D
2002
2003 2004
SUP1-A1
19