Installation of hanging bolt
Use W3/8" (M10) hanging bolts (3 pcs, locally procured).
Matching to the existing structure, set pitch according to size in the unit external view as shown below.
New concrete slab
Install the bolts with insert brackets or anchor bolts.
Anchor bolt
(Blade type
(Slide type bracket)
(Pipe hanging
bracket)
anchor bolt)
Steel frame structure
Use existing angles or install new support angles.
Hanging bolt
Hanging bolt
Support angle
Existing concrete slab
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
Installation of Flow Selector unit
Treatment of ceiling
The ceiling differs according to structure of building.
For details, consult your constructor or interior finish contractor.
In the process after the ceiling board has been removed, it is important to reinforce ceiling foundation (frame) and
to keep horizontal level of installed ceiling correctly in order to prevent vibration of ceiling board.
• Attach the nuts and the W3/8" (M10) flat washers to the hanging bolt.
• Put washers at up and down of the hanging bracket of the Flow Selector unit to hang down the Flow Selector
unit.
• Check that four sides are horizontal with a level gauge. (Horizontal degree: Within 0.2" (5 mm))
Unit
EN-11
Rubber
Hanging bolt (W3/8" (M10))
W3/8" (M10) flat washer (Accessory)
2.0" (50 mm) or less
W3/8" (M10) flat washer (Accessory)
Nut (W3/8" (M10))

External view

Liquid pipe
Discharge gas pipe
Suction gas pipe
Refrigerant pipe connecting port
outdoor unit side
RBM-Y0384FUL
RBM-Y0614FUL
4.7" (120)
3.1" (79)
3.7" (94)
7.1" (180)
RBM-Y0964FUL
1.4" (36)
4.7" (120)
3.1" (79)
3.7" (94)
7.1" (180)
6
Liquid pipe
Gas pipe
Refrigerant pipe connecting port
indoor unit side
Control Box
19.4" (494)
Upper side
(Hanging bolt pitch)
16.8" (425)
(Unit external dimension)
1.4" (36)
4.7" (120)
(Bottom side)
2.4" (60)
22.2" (564)
Upper side
(Hanging bolt pitch)
19.5" (495)
(Unit external dimension)
4.7" (120)
(Bottom side)
2.2" (57)
(Unit:in (mm))
2.4" (62)
0.7" (19)
(Hang-up
3.7" (94)
plate bottom)
2.4" (62)
0.7" (19)
(Hang-up
plate bottom)
EN
EN-12