Basic Configuration - Swegon P.LEMMENS CB2 TAC5 SC Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5.1.3 Heating and/or cooling coil(s) configuration: press ENTER until the item menu « SAT BA? »
appears:
SAT BA?
Select YES, in case of presence of Heating and/or cooling coil(s)
If YES, select the installed coil configuration:
- if heating coil: BA+,
- if water cooling coil: BA-,
TYPE BA?
- if heating/cooling coil (reversible coil): BA+/-,
- if heating coil + one cooling coil (separate): BA+/BA-,
- if electrical coil: KW,
- if electrical coil + one cooling coil: BA-/KW.
Wiring diagram: see appendix 8.
5.1.4 Type of comfort regulation configuration: press ENTER until the item menu « COMFORT » appears:
Select T5 or T2.
COMFORT
Regulation of the comfort T° on supply (T5) or on ambiance (T2). The temperature
ON Tx?
measured on the selected sensor serves as a reference for regulating the heating or
cooling power.
For connections, configuration and user instructions: see installation manual MI ROOM T° SENSOR.
Exit the menu by pressing the SETUP button.

5.2 Basic configuration

This is the configuration of the setpoints for the operation of the unit (airflows, temperatures, ...).
Configuration of the fan is made using the LCD display and the 4 setup knobs. SETUP,
To start the configuration press SETUP until SETUP text appear on the LCD.
The principle of selection is to use keys ↑and ↓ to make the choice and to press ENTER to confirm. The numbers
are introduced figure by figure.
Below you will find a simplified configuration for the use with only one fan.
Complete information is available on the PLC website :
1
LANGUAGE
2
DISPLAY m³h ?
3
DISPLAY Pa ?
4
DISPLAY m/s?
5
TYPE VEN
6
# FAN?
HEATING
7
T°? xx°C
COOLING
8
T°? xx°C
9
MODE
If MODE CA
10
m³h K1?
11
m³h K2?
12
m³h K3?
If MODE LS
10
V min?
11
V max?
12
m³/h≡Vmin
13
m³/h≡Vmin
14
% on K3?
NEXT if MODE CA or LS
CONFIG
15
TIME? N
16
TIME
Language choice
If yes, the airflow of each fan will be displayed on the screen
If yes, the pressure of each fan will be displayed on the screen
If yes, the air speed of each fan will be displayed on the screen (Fill in surface in m²)
Choice of fan through (CID – see label on fan)
Select number of fans connected to CB (F1 or F1+F2).
Only available with post-heating exchanger(s). Select the comfort T° to the heating
exchanger which is connected to the SAT BA.
Only available with post-cooling exchanger(s). Select the comfort T° to the cooling
exchanger which is connected to the SAT BA.
Choice of working mode (CA, LS, CPf, CPs)
Select Airflow 1 for each F1,F2 fan (contacts between terminals K1 and +12V closed)
Select Airflow 2 for each F1,F2 fan (contacts between terminals K2 and +12V closed)
Select Airflow 3 for each F1,F2 fan (contacts between terminals K3 and +12V closed)
Select minimum voltage value for LS link
Select maximum voltage value for LS link
Select airflow for each F1,F2 fan corresponding to Vmin
Select airflow for each F1,F2 fan corresponding to Vmax
Select multiplier of airflow when terminals +12V and K3 are closed ('night' setup).
Select Y to configure time and date
Select Y to activate the time segment scheduling function
www.lemmens.com
,
and ENTER.