Object identifier
OBJECT_ANALOG_VALUE:6 R
OBJECT_ANALOG_VALUE:7 R
OBJECT_ANALOG_VALUE:8 R
OBJECT_ANALOG_VALUE:9 R
OBJECT_ANALOG_VALUE:10 R
OBJECT_ANALOG_VALUE:11 R
OBJECT_ANALOG_VALUE:12 R
OBJECT_ANALOG_VALUE:13 R
OBJECT_ANALOG_VALUE:14 R
OBJECT_ANALOG_VALUE:15 R
OBJECT_ANALOG_VALUE:16 R
OBJECT_ANALOG_VALUE:17 R
OBJECT_ANALOG_VALUE:18 R
* Not applicable for the Flamcomat MK-U G4
Manuel de communication Flextronic
Access
Object Name
Error table 4
(1-error active)
Operational hours total
Availability
( 0 - No, 1 - Yes)
Pressure setpoint
Minimum water level
(absolute)
Level refeeding On
(absolute)
Level refeeding Off
(absolute)
Minimum level alarm limit UINT16 %
Maximum level alarm limit UINT16 %
Nominal volume of vessel
Operational mode
Total refill liters
Total refill minutes
Type
Unit
Range
Bit 0: Maintenance 3 is due
Bit 1: Maintenance 4 is due
Bit 2: Spare
Bit 3: Spare
Bit 4: Spare
Bit 5: Spare
Bit 6: Spare
Bit 7: Spare
UINT16
Bit 8: Spare
Bit 9: Spare
Bit 10: Spare
Bit 11: Spare
Bit 12: Spare
Bit 13: Spare
Bit 14: Spare
Bit 15: Spare
UINT16 hours
Bit 0: P35 M1 pressure increase
Bit 1: P36 M2 Pressure increase
Bit 2: P33 V1 (pressure decrease/ compressor valve)
Bit 3: P34 V2 (pressure decrease/ compressor valve)
UINT16
Bit 4: P31 V3 (filling pump/ valve)
Bit 8: Minimum pressure limiter
Bit 9: Diaphragm rupture sensor
Bit 10: Maximum temperature sensor
UINT16 cbar
0..16000
UINT16 %
UINT16 %
UINT16 %
UINT16 l
0 - single mode,
UINT16
1 - redundant mode
2 - load-dependent
UINT16 l
UINT16 minute
Nous nous réservons le droit de modifier la conception et les spécifications techniques de nos produits.
10