1B. If valve travels too far past open; Manually
rotate shaft CW past the open position.
Follow instructions in 1A for "Setting Open
Position" .
Setting Close Position
2A. If valve did not close completely; Turn power
off. Remove cover. Loosen set screw in
bottom cam and rotate counterclockwise.
Manually rotate shaft clockwise to desired
close position. Slowly rotate cam clockwise
until switch lever opens.
You should hear a light click. (To check using
a multi-meter: Set multi-meter to "Resistance"
or "Continuity" mode. Connect leads to
terminals 3 & 5, rotate cam clockwise until
switch lever opens
& continuity is
achieved.) Tighten
set screw to set
close position.
2B. If valve closed
too far; Manually
rotate shaft
counterclockwise past close position. Follow
instructions in 2A for "Setting Close Position" .

Wiring Diagrams

Electric Actuator
Wiring Diagram
120 VAC/230 VAC
1 Phase
50-60 Hz
Electric Actuator
Wiring Diagram
12-24 VDC and 24
VAC
1 Phase
NOTE: Field wiring is
shown for reference
only: not supplied with
the actuator.
Field Wiring
SW1 – Close
M
SW2 – Open
SW2
SW1
1
2
3
Field Wiring – Low Voltage
SW1 – Close
M
SW2 – Open
SW2
SW1
1
2
3
Restore electric power to actuator and operate
the unit several times and recheck positions.
If still out of alignment, repeat setting cams for
alignment. Replace cover.
Maintenance
Under normal operation, electric actuators require
no formal maintenance program.
Regularly scheduled inspections should be
performed to check for:
Actuator-to-valve misalignment
Damaged housing or mounting hardware
Worn, loose or shifted parts due to shock,
vibration, etc.
Storage
Store in a clean, dry environment and protect from
severe temperature changes and vibration.
NOTE: After Installation it is the customers
responsibility to be certain that all set screws,
terminal screws, housing bolts and mounting
bolts are tight, and limit switches, potentiometers
and position transmitters are calibrated to the
individual settings required for their specific
application.
4
5
6
AC Voltage
4
5
6
AC/DC Voltage
Power to Terminals:
1 and 2 to Open
1 and 3 to Close
Terminals 4 and 5 for field
remote signals
SPDT switch is shown for
illustration only.
Power to Terminals:
1 and 2 to Open
1 and 3 to Close
Terminals 4 and 5 for field
remote signals
+Power to 6 for heater
operation
SPDT switch is shown for
illustration only.
3