5.
Set the Pressure increase Test time to
6.
Press ENTER to confirm.
7.
Deselect Vacuum phase using
8.
Press ENTER to confirm.
9.
Deselect Filling phase using
10. Press ENTER to confirm.
11. Select Process start.
12. Press ENTER to confirm.
The service hoses will now be drained and the A/C service unit's basic menu will be activated. The com-
pressor has produced a slight internal vacuum so that the filter can be replaced with minimal refrigerant
loss.
13. Switch off the A/C service unit.
14. Pull out the power supply plug.
15.
CAUTION! Health hazard The following steps may only be performed by authorized personnel.
Wear protective gloves and goggles.
Unscrew the screw (D) from the holder, and pull the dryer filter straight out.
16. Replace the O-rings (E). Moisten new O-rings with refrigerant oil before installing.
17. Insert the new dryer and tighten the screw to max. 15 Nm.
18. Reconnect the power plug.
19. Switch on the A/C service unit.
The inverter performs a self-test.
20. Reset the R1234yf from system counter
21. Perform a leak test
24
1
.
No
.
No
(Resetting the counters
(Leak test
on page 22).
.
on page 23).