Installation
How to select installation position
1. If the unit is to be installed on the floor, its undercarriage should be heightened, to avoid ingression of
accumulated water in rainy season. In snowy areas, it is important to prevent accumulated snow from
blocking up the air-out. The recommended height is 20cm to 30cm.
2. Drain ditch or other facilities should be arranged under the outdoor unit, to avoid the environment
influence because of water discharge.
3. To install the unit at balcony or top of building, the installation site must meet the allowable bearing
capacity of building structure, without affecting the structural safety.
4. Ensure the unit is well ventilated, direction of air exhaust is kept away from windows of neighboring
buildings, and the exhaust air cannot flow back. Moreover, adequate service clearance should be kept
around the unit.
5. The unit should not be installed at places accompanied with oil, inflammable gas, corrosive components
e.g. sulfur compound, or high-frequency equipment.
6.
The unit must be installed on reliable base or framework. Weight capacity of framework should be 3
times of the body weight, and safeguard measures should be taken to avoid malfunction of fastenings.
7.The unit should not be installed at sites with typhoon/ earthquake hazards. Midair installation should be
avoided as much as possible as machine falling down may result in severe accident.
Installation in exceptional circumstances (unit: mm)
No obstacle in front of the unit
≥50 0
ENGLISH
Installation must be carried out by professional
≥50 0
≥50 0
Obstacle in front of the unit, several units in a row
Note!
Obstacle above the unit
≥500
≥500
≥500
6
≥500