SECTION 5 |
be disabled to prevent overcharging of the battery (see details under
at Section 4.1.3). A DIP Switch (4 in Figs 2.1 to 2.3) is provided on top of the output
terminals for selecting the battery type and for disabling the Boost Stage when charging
loaded batteries. The following selections can be made with the help of the DIP Switch.
!
CAUTION!
Do not change the DIP Switch setting when the charger is operating. Always
change the DIP Switch setting when the charger is off , i.e. after disconnecting
the charger from the AC input power.
NOTE: The voltages are for a temperature of 80°F.
!
CAUTION!
Please ensure that the position No. 4 of the DIP switch (S1-ON & S2-ON) is
NEVER selected.
TABLE 5.1 DIP SWITCH SETTINGS: SEC-1215UL/SEC-1230UL
S1
S2
OFF *
ON *
ON
OFF
OFF
OFF
ON
ON
* Factory pre-set in this position
TABLE 5.2 DIP SWITCH SETTINGS - SEC-2415UL
S1
S2
OFF *
ON *
ON
OFF
OFF
OFF
ON
ON
* Factory pre-set in this position
Installation & Charger Operation
Float
13.5 V *
14.4 V *
13.5 V
14.0 V
13.5 V
Disabled
Caution! Do NOT use this setting
Float
27 V *
28.8 V *
27 V
28.0 V
27 V
Disabled
Caution! Do NOT use this setting
Battery
Boost
Type
Flooded /
AGM *
Gel Cell
Battery with
Load
Battery
Boost
Type
Flooded /
AGM *
Gel Cell
Battery with
load
CAUTION!
!
Charging
Stages
3 Stages
(Stages 1, 2, 3)
3 Stages
(Stages 1, 2, 3)
2 Stages
(Stages 1, 3)
Charging
Stages
3 Stages
(Stages 1, 2, 3)
3 Stages
(Stages 1, 2, 3)
2 Stages
(Stages 1, 3)