Elkron HPA700MF Mode D'emploi page 7

Un dispositif sonore et optique d'alarme feu
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Terminal block
+IN
IN-
+OUT
OUT-
Note: the negative of the power supply is not connected to the negative of the alarm circuit that is an
opto-isolated section; the negative alarm circuit must be connected to the same power source that
provides the positive alarm circuit (siren output).
A
B 2
OFF
OFF
OFF
ON
ON
OFF
ON (*)
ON (*)
(*) Default setting
Remaining micro-switches are unused.
INSTALLATION
Figure 2 - View of the bottom of the siren – dimensions in mm
Install the siren following the instructions reported below:
Remove the front cover from the siren unscrewing the front screw.
Break the plastic cable passage.
Install on a wall using the relevant fixing holes placed on the bottom of the enclosure (as
illustrated in figure 2).
Perform the electrical connections.
Put back the front cover and fix it screwing its front screw.
AL Alarm circuit – Terminal blocks
Description
24V⎓ positive alarm circuit input coming from the fire control panel (siren
output) or the sirens/bells in cascade.
Negative alarm circuit input coming from the fire control panel (siren
output) or the sirens/bells in cascade.
24V⎓ positive alarm circuit output for driving other devices connected in
cascade.
Negative alarm circuit output for driving other devices connected in
cascade.
Acoustic tone - Jumpers
Description
Tone 1 – frequency sweep 800970Hz in 1s
Tone 2 – two tones 610Hz for 0.5s and 920Hz for 0.5s
Tone 3 – pulsed 920Hz for 0.5s ON and for 0.5s OFF
Tone 4 – continuous 920Hz
Fixing
hole
Cable
passage
Fixing
hole
148
7/20
Fixing
hole
Fixing
hole