Safety instructions for installation, maintenance and operation
Installation and usage
Prior to commencing installation or usage read
instructions carefully and follow all directions! Pass
these instructions on to the system operator and
retain for later reference!
Warning! Installation and maintenance is to be
done only by competent and qualified professionals
qualified for sanitary plumbing. Electrical installation
is to be done only by professionals
qualified for electrical facilities!
Warning! Local standard and rules for sanitary
plumbing as well as accident prevention must be
adhered to as a matter of priority.
Note! It is essential that following the installation
a leak test of the water-bearing components as well
as a functional test is carried out.
Danger! To isolate from mains
disconnect the mains plug prior
commencing any maintenance work.
Usage
The Water Supply Set Plus shall only be used as a
secondary inlet (for drinking- or rainwater) for the
FK-5 break tank station. Each other usage is consi-
dered contrary to the designated use.
Warning information
Please read and follow the warning
information in these instructions.
Disregard of the warning information may lead to
injury or material damage!
Labelling of important warning information:
Danger! Electricity!
Indicates hazards that might result in
severe or fatal injury.
Warning! Indicates hazards that may
lead to injury, material damage or
contamination of drinking water.
Note! Indicates hazards that may lead
to damages to the system or
malfunctions.
Important notes for the system operator
Medium: Water
Max. ambient temperature 39°C,
Min. ambient temperature 2°C,
Max. temperature of the inflowing medium 35 °C,
Min. temperature of the inflowing medium 1 °C,
Minimum flow pressure DN 20 = 1 bar / 0.1 MPa,
Minimum flow pressure DN 25 = 1.5 bar / 0.15 MPa,
Max. flow pressure 20 / 25 4.0 bar / 0.4 MPa,
pressure stage PN 10,
Outlet pump pressure
DN 20: 4.3 bar / 0.43 MPa
DN 25: 5.9 bar / 0.59 MPa
Only use the device
- in sound condition
- as intended
Warning! Any water withdrawn must
under no circumstances be used as
drinking water - even in small amounts!
Warranty
Warranty is voided through:
- Disregard of installation instructions.
- Damage due to faulty installation.
- U nauthorised product modifications.