The Relay Control Card AS400 DB9 port offers users the solution for UPS status
monitoring via 5 output relays. In addition, it provides 1 input contact to perform UPS
shutdown in battery mode. This card is compatible with UPS devices with expansion
slot.
Internal Circuit
AS400 Card Pin out
Pin Assignment
Pin1
UPS FAULT
Pin2
SUMMARY ALARM
Pin3
GND (Common for Pin4)
Pin4
REMOTE SHUTDOWN
Pin5
COMMON (For Relays)
Pin6
BYPASS 1 / UPS OFF
Pin7
BATTERY LOW
Pin8
UPS ON
Pin9
UTILITY LINE FAIL
Note: All relay contacts are normally open (N.O.) except for Pin6. Acceptable Power +
Vcc for Pin4 is 7.5 – 12V, 0.0672W Max
1
For online series UPS models only.
Installation guide
The AS400 card is hot-swappable and can be installed while the UPS is on.
1- Remove the two retaining screws on the expansion slot cover, and then remove the
cover.
2- Install the AS400card into the expansion slot.
3- Re-install and tighten the retaining screws.
Function Description
Status
Pin1 short to Pin5
Pin2 short to Pin5
Pin6 short to Pin5
Pin7 short to Pin5
Pin8 short to Pin5
Pin9 short to Pin5
Example application
Supply 12VDC to the COMMON contact and connect LEDs to the DB-9 port pins 1, 2
and 6 to 9. Connect a push button to COMMON (Pin5) and REMOTE SHUTDOWN
(Pin4). Pressing the button for at least 5 seconds will shut down the UPS when it is on
battery.
Note : When the UPS is on battery, the REMOTE SHUTDOWN input (Pin4 & Pin3)
accepts at least 5 seconds of high level signal (+12VDC) to perform the UPS shutdown.
UPS output power will turn off after 120 seconds.
2
INFOSEC UPS SYSTEM – 15 rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
Hot Line Tel: +33 (0)2 40 76 15 82 – fax: +33(0)2 40 94 29 51 – hotline@infosec.fr – 10 20 AA 36 203 11
Function
I/O
O/P
O/P
Power GND
Power + Vcc
O/P
O/P
O/P
O/P
O/P
Condition
UPS fault
Summary alarm
UPS is OFF. / UPS is in Bypass Mode. 1
Battery Low
UPS is on.
Utility Line Fail
Technical specification
Electrical
External S/D Voltage
Power Dissipation
Physical
Dimensions (WxHxD)
Weight
Environmental
Operating
Temperature
Operating Humidity
Output Relay Rating
Voltage
30VDC /250VAC
AS400 card DB9 Pin
7.5V – 12V
1.35W Max
(Default 12V input)
41.8 x 14.2 x 81mm
(1.65 x 0.6 x 3.2 in)
52g (1.92oz)
0° C – 40° C (32° F - 104° F)
0% – 95% (Non-condensing)
Maximum
Current
3A (per relay)