This is a brief document designed to quickly get you started setting up your valve manifold with an integrated
Numatics' G2-2 CANopen communication node.
1) Initial Unpacking and Inspection
1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.
2) Remove wrapped manifold assembly from box.
a) Remove manifold assembly from anti-static packaging
b) Retain documentation for installation and configuration
3) Examine manifold assembly for any shipping damage such as:
a) Bent pins or connectors
b) Report any damage to shipping carrier immediately
4) Examine manifold assembly for proper ordered configuration. (Valves, I/O, Protocol, etc.)
2) G2-2 Introduction
Below is an example of a 2012 series valve manifold. This fieldbus manifold series is capable of addressing a
total of 224 I/O. The manifold can be viewed as having two sections to it, the
Side
Valve Side
. The
maximum of 6 modules totaling 192 Outputs, 96 Inputs, or various combinations. The communication
module has two connectors: a 5-pin communication connector and a 4-pin power connector. Pin-outs for
these, along with I/O connectors, are labeled on the side of the respective modules.
Dual 25 Pin Sub-D
w/Aux Power Output Module
Analog Module
G2-2 Series CANopen Quick Start Manual
supports a maximum of 32 solenoid coils and the
Discrete I/O
Connectors
I/O Point
LED Status
Indicator(s)
19 Pin Round
Connector Module
8 Connector I/O Module
3835053 TDG22COQS1-1
Subject to change without notice
www.numatics.com/fieldbus
Discrete I/O Side
Discrete I/O Side
(Maximum of 6 Modules)
Module/
Network
Status LED's
RUN
ERROR
CANopen
FUSE 1
+24V VLV/OUT
FUSE 2
+24V NODE/IN
Manual Configuration
Terminal Strip Module
Module (MCM)
5/07
Valve Side
and the
Discrete I/O
supports a
Valve Side
(Maximum of 32 Solenoids)
Chassis Ground
Connection
Valve
End Plates
Valve
Valve Side
Sub-D Output
Module
Communications
Module
Solenoid LED
Status Indicator
Manual
Override
Page 1

Publicité

Table des Matières
loading

Sommaire des Matières pour Emerson numatics G2-2 Série

  • Page 1 G2-2 Series CANopen Quick Start Manual Getting Started This is a brief document designed to quickly get you started setting up your valve manifold with an integrated Numatics’ G2-2 CANopen communication node. 1) Initial Unpacking and Inspection 1) Examine exterior of package for signs of damage. Report any damage to shipping carrier. 2) Remove wrapped manifold assembly from box.
  • Page 2 G2-2 Series CANopen Quick Start Manual 3) MCM - Manual Configuration Module DIP Switch Rotary Switch (SW2) (SW3) DIP Switch Rotary Switch (SW1) (SW4) 5 6 7 8 5 6 7 8 All DIP switches shown in the "OFF" position The MCM is the module that allows the user to manually set baud rate, MAC ID and other user definable options.
  • Page 3 G2-2 Series CANopen Quick Start Manual MCM Settings DIP Switch Settings (SW1) Baud Rate: SW1-1 SW1-2 Kbaud Off* Off* 125* 1000 Manual or Software Configuration: Switch Setting Description SW1-5 MCM Disabled - Ignore MCM Settings SW1-5 MCM Enabled - Use MCM Settings DIP Switch Settings (SW2) Hundreds Digit: Switch...
  • Page 4 G2-2 Series CANopen Quick Start Manual 4) Self-Test Mode An internal diagnostic tool can also be enabled using the optional MCM module. This tool allows the user to confirm that all of the Inputs and Outputs on the manifold are fully functional without needing a network connection or controller.
  • Page 5 G2-2 Series CANopen Quick Start Manual 5) I/O Mapping Example Example: Assumed Settings - Single Z-Boards used with single solenoid valves - Double Z-Boards used with double solenoid valves Discrete I/O Configuration Objects Module Type Part No. 239-1384 8O Sourcing 239-1315 (PNP) 16O Sourcing...
  • Page 6 G2-2 Series CANopen Quick Start Manual I/O Mapping Table Example Continued Output Table SUB-INDEX Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Valve Coil Valve Coil Valve Coil Valve Coil Valve Coil Valve Coil Valve Coil Valve Coil...
  • Page 7 G2-2 Series CANopen Quick Start Manual 6) Output Short Circuit Protection (Status Input Bits) Status Input Bits report the integrity of the load being driven by the output driver. They must be mapped to the scanner as part of the Input Size Value. Please refer to the table below for Status Input Bit action during fault condition: Output Type Output State...
  • Page 8 G2-2 Series CANopen Quick Start Manual 8) Communication Module Connector Pin-Outs CANopen Communication Connector Pin-Out Pin No. Function Description Shield Cable shield Bus Power, 11-25VDC Bus Power, Common CAN_H Controller Area Network High, Communication Line CAN_L Controller Area Network Low, Communication Line Auxiliary Power Connector Pin-out Standard Function...
  • Page 9: Led Functions

    G2-2 Series CANopen Quick Start Manual 9) LED Functions Upon power up, the LEDs indicate the status of the unit. There are six LEDs on the G2-2 CANopen node; one for Run, one for Error, two for internal fuse integrity and two for Aux. Power status. ERROR CANopen FUSE 1...
  • Page 10 G2-2 Series CANopen Quick Start Manual 10) PDOs PDOs or Process Data Objects are used to transfer the real time data (I/O) with no protocol overhead. The G2-2 series supports four transmit and four receive PDOs defined in the Pre-Defined Connection Set. Each PDO can transfer up to eight bytes of data.
  • Page 11: Factory Default Settings

    G2-2 Series CANopen Quick Start Manual 12) Factory Default Settings Unless otherwise requested, all standard G2-2 Series CANopen manifolds ship with specific factory default settings. Below is a list of the factory default settings: Description Default Settings Node Address Baud Rate 125 KB Input Module Power Jumper (Input sensor power supplied by...
  • Page 12: Pour Commencer

    Guide de Démarrage Rapide Série 2-2 - CANopen Pour commencer Ce document décrit le démarrage rapide de votre îlot de distribution à nœud de communication CANopen série G2-2 intégré. 1) Déballage et inspection 1) Inspectez l'emballage extérieur pour détecter tout dommage. Tout dommage constaté doit être signalé au transporteur.
  • Page 13: Mcm - Module De Configuration Manuelle (Option)

    Guide de Démarrage Rapide Série 2-2 - CANopen 3) MCM – Module de configuration manuelle (option) DIP Switch Rotary Switch (SW2) (SW3) DIP Switch Rotary Switch (SW1) (SW4) 5 6 7 8 5 6 7 8 All DIP switches shown in the "OFF" position Le MCM (module de configuration manuelle) permet à...
  • Page 14 Guide de Démarrage Rapide Série 2-2 - CANopen Réglages du MCM Réglages des DIP switchs (SW1) Taux Baud : SW1-1 SW1-2 Kbaud Off* Off* 125* 1000 Configuration manuelle ou par logiciel : Switch Réglage Description SW1-5 MCM désactivé – Ignorer les réglages MCM SW1-5 MCM activé...
  • Page 15: Mode Auto-Test

    Guide de Démarrage Rapide Série 2-2 - CANopen 4) Mode auto-test Un outil diagnostic interne peut également être activé par le module MCM optionnel. Cet outil permet à l'utilisateur de s'assurer que toutes les entrées et sorties sur l'îlot sont complètement opérationnelles, sans besoin de connexion réseau, ni de contrôleur.
  • Page 16 Guide de Démarrage Rapide Série 2-2 - CANopen 5) Exemple de mapping des E/S Exemple: Réglages présumés - Cartes Z-Boards simples utilisés avec les électrodistributeurs simples. - Cartes Z-Boards doubles utilisés avec les électrodistributeurs doubles. Configuration des E/S discrètes Objets Type de Code module...
  • Page 17 Guide de Démarrage Rapide Série 2-2 - CANopen Exemple de mapping des E/S - continuation Tableau des sorties SUB-INDICE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 6200 01 08 Bobine no. 8 Bobine no.
  • Page 18: Protection Des Sorties Contre Les Courts-Circuits (Bits D'entrée D'état)

    Guide de Démarrage Rapide Série 2-2 - CANopen 6) Protection des sorties contre les courts-circuits (bits d'entrée d'état) Les bits d'entrée d'état signalent l'intégrité de la charge pilotée par le pilote de sortie. Ils doivent être mappés sur le scanner comme partie de la valeur de la taille de l'entrée. Voir le tableau ci-dessous pour l'action du bit d'entrée d'état lors de l'occurrence d'une condition de défaut: Type de sortie Etat de sortie...
  • Page 19: Affectation Des Broches Du Connecteur Du Module De Communication

    Guide de Démarrage Rapide Série 2-2 - CANopen 8) Affectation des broches du connecteur du module de communication Affectation du connecteur de communication CANopen No. de Fonction Description broche Blindage Blindage de câble Tension bus, 11-25VCC Tension bus, commun Réseau CAN (Controller Area Network) high, ligne de CAN_H communication Réseau CAN (Controller Area Network) low, ligne de...
  • Page 20: Fonction Des Voyants Led

    Guide de Démarrage Rapide Série 2-2 - CANopen 9) Fonction des voyants LED A la mise sous tension, les voyants LED indiquent l'état de l'unité. Le nœud CANopen G2-2 dispose de six voyants LED; un pour Run (Exécuter), un pour Error (Erreur), deux pour l'intégrité des fusibles internes, et deux pour l'état de l'alimentation Aux.
  • Page 21: Configuration Canopen

    Guide de Démarrage Rapide Série 2-2 - CANopen 10) PDO (objets de données process) objets de données process Les PDO (Process Data Objects = ) sont utilisés pour transmettre les données temps réel (E/S) sans surcharge de protocole. La série G2-2 supporte quatre PDO de transmission et quatre PDO de réception définis dans les objects de communication prédéfinis (Pre-Defined Connection Set).
  • Page 22: Réglages Par Défaut Programmés En Usine

    Guide de Démarrage Rapide Série 2-2 - CANopen 12) Réglages par défaut programmés en usine Sauf demande contraire, tous les îlots standard CANopen série G2-2 sont fournis d'usine avec les réglages par défaut . Ci-dessous une liste des réglages par défaut. Description Réglages par défaut Adresse du nœud...

Table des Matières