Positionneur digital

Commands

#
Display
1
Auto
Perform Auto Initialization
Restore Last Autocalib Data
2
RsCl
3
InCl
Perform Input Calibration
4
DRes
Reset Diagnostic Data
22.1

Auto Initialization Procedure

The Auto item move to the sub-menu that manages the Initialization procedure, the user can select
two auto initialization modes:
Full Auto: (Go Auto)
The user has just to move the actuator (by D and I key switches) round to middle of the total stroke.
The procedure moves the actuator to the full open and close limits and operates a series of movements in order to evaluate
the characteristic of the actuator.
a
Pre- conditions required to start the Full Auto Initialization:
The actuator must be mounted and adjusted complete on the control valve. Limit switches open/ close must be
adjusted regarding the real stroke of the control valve.
+pls. note cut off modes (limit or torque switch)
a
During the initialization, the limits of the actuator/ valve will be reached
It must be ensure that this can be performed without any risks
Manual Limit Setting: (Go Man)
+
pls. note: By using the Manual Limit Setting Function, the user has to ensure that the Close Tight Functions
is disabled, otherwise an positioning error will be occurred, caused by over traveling the actuator limits. (up/down)
The user has to move the valve first to the full open position (by D and I key switches), confirm (by A/M key switch)
in order to store the position, then the same for the full close position. On the full close position confirm (by A/M key switch),
the automatic procedure to evaluate the characteristic of the valve is started.
On completion of the procedure the result is prompted to the user (Success or Failure) and the device waits for
user acknowledge; pressing the A/M key switch the unit stores the new calibration data and exits to the normal
operation mode if the procedure was successful, or back to the first step of the procedure.
a
Anytime long press (more than 4 sec) of the A/M key switch aborts the procedure and exits to the
normal operation mode; no new data is stored.
Description
Enter to the Initialization procedure
Restore the dead band to the value calculated by the last auto-
Initialization procedure, user changes are cancelled
Enter to the analogue input calibration procedure
Reset of the diagnostic counters