Description
GB
Item M7TIC/ELE is an electronic device intended for use in monitoring systems associated with MEGATIKER electronic breakers which can obtain
all the information on the state of the protection unit, converted into one of the most common formats in industrial applications, the Modbus protocol
on RS-485, in the RTU and ASCII modes.
This information includes for example the protection state (pre-alarms, alarms, etc.), the history (causes of the last operation with indication
of the phase involved, operation counters, etc.), the electrical and thermal magnitudes (phase and leak to earth currents, card operating temperature,
etc.) and the protection state information (threshold levels set, rated current of the switch, number of poles, etc.).
1
M e
- 4 8
R S
+
-
1
V
2 4
Configuration
A1-3 – Modbus Address.
The Modbus address is defined by configuring the first three positions.
Each of these can be worth "no configurator" = 0, 1‚ 9.
The address value (in decimal, values allowed 1÷247) is obtained as follows:
A1· 100 + A2· 10 + A3
Example:
A1=2, A2=3, A3= "no configurator":
the address value is 230.
M – Modbus Transmission mode.
The transmission mode is defined as follows:
➩ ASCII modes
- 1
➩ "not allowed"
- "other values"
➩ "default" (RTU mode)
- "no configurator"
B – Modbus Transmission Speed.
The transmission speed is defined as follows:
➩ 1.2kbit/s
- 1
➩ 2.4kbit/s
- 2
➩ 4.8kbit/s
- 3
➩ 9.6kbit/s
- 4
➩ 19.2kbit/s
- 5
➩ 38.4kbit/s
- 6
➩ "not allowed"
- "other values"
➩ "default" (speed 9.6kbit/s)
- "no configurator"
1
2
Megatiker
RS-485
4
3
2
R
- + SG
r
t i k e
g a
1
2
5
S G
24V
M7TIC/ELE
2
E
/ E L
T I C
M 7
R
1
Power supply (+)
2
Power supply (-)
3 4
3
Serial port – Tx
R
4
Serial port – Rx
Note:
for correct operation of the communication with the
MEGATIKER the Tx and Rx cables of module M7TIC/ELE
must be connected to the Rx and Tx terminals
of the protection respectively (see wiring diagram).
-
Tx/Rx Rs485
+
Tx/Rx Rs485
SG
Signal mass
R
Power supply 24V – ~
1
Power supply 24V – ~
2
Note:
use power supplies with double insulation or equivalent
LED. When the application is running:
- slow flash: "stand-by" mode
- fast flash: transmission/receiving in progress
R S
-
1
4
3
2
1
R
r
t i k e
g a
M e
5
- 4 8
S G
+
2
E
/ E L
T I C
V
2 4
M 7
R
e
A1
A2
A3
M
B
(not managed)