Télécharger Imprimer la page

SOMFY animeo IB+ 4 Notice D'installation page 10

Masquer les pouces Voir aussi pour animeo IB+ 4:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 9
GB
A
PICTURES
[1] IB+ 4 AC Motor Controller WM-O 220-240 V AC,
Ref. 1860231
[2] RTS Radio Module, Ref. 1860105
[3] Telis 4 RTS Pure, Ref. 1810631
[4] Philips OSD Interface, Ref. 11544100
[5] Philips Motion Sensor, Ref. 73234399
B
MOUNTING
[1] Choose the optimal location: sufficient surface area
[2] Mounting of the IB+ 4 AC Motor Controller WM-O
C
WIRING
[1] Tool for all terminals
[2] Wiring diagram
[3] Check the correct running direction of the
endpro ducts (group and local control inputs).
UP: end product moves upward
STOP: end product stops
DOWN: end product moves downward
CABLE
Connection to ...
Motors
Motor Controller Exten-
sion
Switch
IB+ bus
220 - 240 V AC
Cables
Min.: 4 x 0.75 mm
/19 AWG
2
Max.: 4 x 2.5 mm
/14 AWG
2
Min.: 2 x 0.25 mm
/24 AWG
2
Max.: 2 x 0.75 mm
/18 AWG
2
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 2.5 mm
/14 AWG
2
Min.: 4 x 0.6 mm/22 AWG
Max.: 4 x 1.5 mm
/16 AWG
2
Min.: 3 x 1.5 mm
/16 AWG
2
Max.: 3 x 2.5 mm
/14 AWG
2
D
CONFIGURATION
[1] Reset / Prog button
With this button, you can access the basic
configuration of the Motor Controller.
[2] Selection of switch ergonomic
Local push button ergonomics and the type of
end products to be preselected:
• Screen mode (SCR)
• Venetian blind, European mode (default mode)
• Venetian blind, US mode
1.
To toggle between modes, press shortly the
Reset / Prog button. Repeat until the LED,
according to the desired configuration, lights up.
2.
Save and exit
[3] Factory RESET
[4] Learn running and tilting times/length
1.
Press immediately when lower end limit
is reached
2.
Maintain stop for duration of tilting
3.
Release immediatly after complete turn
[5] Learn and recall intermediate position (IP)
1.
Recording
2.
Recalling
[6] Symbols: actions
1.
Up
2.
Stop
[7] Symbols: end product status
1.
Up
2.
High position
3.
Down
4.
Low position
5.
Stop at the required position
6.
Short up and down movement
7.
Intermediate position (IP)
When electronic motors are to be controlled through this
Motor Controller device it is mandatory to configure the
start-up delay time for electronic motors in the Motor
Controller settings. To configure the start-up delay time WT
Setting Tool Ref. 1811242 can be used.
Twisted pairs
Required
Recommended
Recommended
animeo IB+ 4 AC MOTOR CONTROLLER WM-O . REF. 5111192-C -
Max. distance
150 m
50 m
100 m
1000 m