Télécharger Imprimer la page

IME Nemo SX Mode D'emploi page 8

Masquer les pouces Voir aussi pour Nemo SX:

Publicité

Les langues disponibles

Les langues disponibles

Nemo SX - Energy Web Server
5. GENERAL CHARACTERISTICS
Web pages access:
. Access to the web Servers pages and data is secured by two
identification codes (PIN and PUK codes).
. Four types of "default" users are configured:
User
administrator
99999
Installer
55555
user
11111
Note: The home page ("home") will be different depending on the
type of user that access to the device
.
manual)
Historical of consumptions
. All energy, water and gas values (Δ of consumptions and global
counters) and statistical values (average values, peak values, etc.),
only if available on the device making the measurement, are saved
automatically in files ".CSV" compatibles with Excel or "csv" reader.
. Access to this data is possible in several ways:
- "FTP" protocol
- creation of a network drive
- data download via web pages
- receive automatic reports sent by the web server
(for more details refer to the user manual)
Data storage time:
. Energies (Ea+), Water consumption, Gas Consumption: data
storage time is unlimited.
Sampling of data (accuracy per minutes) is over time reduced, thus
passing to an accuracy per hour → per day → per month → per year
for the oldest stored data.
. For data such as:
THD
(if available on the measuring device installed)
Harmonics
(if available on the installed measuring device)
Min, max, average values
(if available on the measuring device installed)
Status information
(if available on the device installed)
the storage time is limited according to:
total number of registered devices
number of "EQ" devices activated
type of registered devices (e.g. Energy meter, Multifunction
devices, ...)
Sampling of data (accuracy per minutes) is over time reduced, thus
passing to an accuracy per hour → per day → per month → per year
for the oldest stored data.
Real Time Clock battery:
. 3 V / 210 mAh
Pollution degree
:
. 2
Ambient operating temperature:
. Min. = 0°C. Max. = +40°C
Ambient storage temperature:
. Min. = -40°C. Max. = +85°C
Technical data sheet: IDP000174EN_02
(continued)
PIN
PUK
00000 9999 00000
00000 5555 00000
00000 1111 00000
(for more details refer to the user
.
Cat. N°: SXWS255
5. GENERAL CHARACTERISTICS
Relative humidity:
. 95% @ 40°C (non-condensing)
Case material:
. Aluminium housing
Protection Index:
. Protection index against direct contacts:
IP2X (IEC/EN 60529).
Vibrations during operation:
. 3G rms, IEC 60068-2-64, random, 5 ~ 500 Hz, 1hr/axis
Shocks during operation:
. 30G rms, IEC 60068-2-27, half sine, 11ms duration
Consumption:
. Typical 6,9 W
. Max 11,5 W
Average weight per device:
.
. 0,8 kg
Volume when packed:
.
3
. 7,75 dm
6. COMPLIANCE AND APPROVALS
Compliance to standards:
. Compliance with Directive on electromagnetic compatibility (EMC)
n° 2014/30/EU
. Compliance with low voltage directive n° 2014/35/EU.
. Electromagnetic Compatibility:
EN 55011: 2016
EN 55022: 2010 + AC: 2011
EN 55024: 2010 + A1: 2015
EN 61000-6-4: 2007 +A1: 2011
EN 61000-3-2: 2014
EN 61000-6-2: 2005 +AC: 2005
EN 61000-3-3: 2013
EN 61000-4-2: 2009 / EN 61000-4-3: 2006 +A1: 2008 +A2: 2010
EN 61000-4-4: 2012 / EN 61000-4-5: 2014 / EN 61000-4-6: 2014
EN 61000-4-8: 2010 / EN 61000-4-11: 2004
Environment respect – Compliance with EU directives:
. Compliance with Directive 2011/65/EU modified by directive
2015/863 (RoHS 2) on the restriction of the use of certain hazardous
substances in electrical and electronic equipment.
. Compliance with REACH regulation: at the date of the publication
of this document no substance from the candidate list is present in
these products.
Packaging :
. Design and manufacture of packaging compliant to decree 98-638
of the 20/07/98 and also to directive 94/62/CE.
Updated: 14/02/2018