Settings
Installation and operating manual: PLATINUM PhaseBalancer
12
Version 05/2010
Mat. No. 742 679-AA
Operating mode
Key
ST
Select operating mode.
ESC
Back to the Main Menu
OK
Switch to selected operating mode.
OFF
Î
Switch off PhaseBalancer function.
Î
No limit of unbalanced load.
POWER CONTROL
Î
Switch on PhaseBalancer function.
Î
Inverter monitors and limits the difference of the AC output.
ERROR OFF
Î
If an inverter fails, the other inverters are also disconnected from
the network (e.g. in case of a permitted unbalanced load of 0 W).
ERROR REDUCE
Î
If an inverter fails, the two other inverters limit the AC output to
the set unbalanced load .
Function