EFRIGERANT RECOVERY
a)
Connect the refrigerant circuit to the recovery unit by means of flexible hoses with ball
valve, as shown by the picture.
b)
Turn the V1 valve to position Recovery
c)
Turn the INPUT valve to position "CLOSE" Make sure the Recover/Purge valve is on
the RECOVER position.
d)
Connect the T2 flexible hose valve (delivery) to the recovery cylinder.
e)
Open the valves on the manifold (manifold is not supplied with the unit)
f)
Open the recovery cylinder's valve
g)
Open the T1 and T2 flexible hoses valves (flexible hoses are not supplied with the unit)
h)
Turn the Power Switch to position "ON"
i)
Turn the BY-PASS switch to position "MANUAL"
j)
Press the START key to start the unit
WIGAM
USER'S MANUAL
IMPORTANT
Make sure that the V1 valve is on position "Recovery"
ENGLISH
32