Electrical Details; Maintenance Recommendations - Domnick Hunter PNEUDRI MINI Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 22

6. ELECTRICAL DETAILS

This only applies to electrically powered units.
Component qualified electricians must work on dryer circuitry.
Check the rating plate for power supply requirements.
Correct isolator switches must be provided at a safe and accessible point near the dryer.
The dryer must be connected with a live, neutral and earth.
NOTE 50mA fuse protection is required but is not included as part of this package.
It is possible to operate the cam timer from 240 volt single phase 50Hz supplies by connecting as
indicated in the wiring diagram below. Should you be connecting to 110v 50Hz or 60Hz supplies
please ensure that the necessary non standard cam motor has been requested and supplied before
attempting connection.

7. MAINTENANCE RECOMMENDATIONS

Weekly
Ensure drain function / operation on all upstream drains is satisfactory.
Ensure that the changeover occurs approximately every 2 minutes.
Check all the gaskets, control valves, pipes, and fittings for air leaks.
The desiccant material used has a finite life but would typically exceed 10,000 hours. Desiccant
replacement should be undertaken at this interval or when it has become contaminated.
The filter requirements also have a finite life typically lasting 6,000 - 8,000 hours.
For desiccant changes or any other maintenance operation, service kits are available.
GREEN
BLUE
MOTOR
BLACK
Earth
Live
Neutral
6