Gira 5473 00 Manuel D'utilisation page 6

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Capteur d'énergie radio quadruple
Channel settings
Parameters
Active energy
Extended channel settings
Parameters
Manual commissioning
Transmit voltage
Transmit current
Transmit effective power
Transmit reactive power
Transmit apparent power
Transmit absolute active ener-
gy
Transmission interval
32582012
10864966
Setting options, Basic set­
ting
-1073741823...1073741823
Wh
Basic setting: 0 Wh (Current
value)
Setting options, Basic set­
ting
On, Off
Basic setting: On
On, Off
Basic setting: On
On, Off
Basic setting: On
On, Off
Basic setting: On
On, Off
Basic setting: On
On, Off
Basic setting: On
On, Off
Basic setting: On
1 ... 60 min
Basic setting: 15 min
10.04.2017
Explanations
Displays the currently cumula-
ted active energy. The value
can be reset to 0 or set to any
other value.
Explanations
Blocks manual commissioning
for the device channel. In the
"Off" setting, the device can-
not be reset to the factory set-
ting.
Transmits the current voltage
value.
Transmits the current current
value.
Transmits the average effec-
tive power. If negative values
are displayed, then effective
power is fed in, e.g. via a pho-
tovoltaic system.
Sends the current fundamen-
tal oscillation idle power value.
If negative values are dis-
played, this is capacitive reac-
tive power. Positive values
show an inductive reactive po-
wer.
Transmits the current appa-
rent output value.
Transmits the cumulative va-
lue of the active energy. If ne-
gative values are displayed,
then effective energy is fed in,
e.g. via a photovoltaic system.
The current consumption data
is transmitted at the interval
set here at the latest. Changes
to the effective power cause
fresh transmission, however
only after one minute at the
earliest.
6/8

Publicité

Table des Matières
loading

Table des Matières