Secondary Air; Flue; Chimney Pot; Connection To The Chimney - Nordica MAX - JUNIOR Instructions Pour L'installation, L'utilisation Et L'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

MAX - JUNIOR / MAJOR - MINOR
stoves MAX and JUNIOR are equipped only with the primary air control, as the secondary air is pre-adjusted.
1A - PRIMARY air register
With the register below on the door of the hearth it is adjusted the passage of air through the drawer of ash and the grate in the fuel
direction. The primary air is necessary for the combustion process. The ash drawer must be regularly emptied, so that the ash does
not obstruct the primary air entry for the combustion. Through the primary air the fire is also kept alive.
During wood combustion, the register of primary air must be opened only for a while, because otherwise the wood burns fast and the
stove may overheat. The register is open when the lever is completely pulled out. The register is closed when the lever is introduced
(see chapter NORMAL OPERATION).
2A - SECONDARY air register
On the over part of the door there is the secondary air control. Also this control must be opened, especially for wood combustion, so
that unburnt carbon does not undergo a post-combustion (see chapter NORMAL OPERATION).
The adjustment of the registers necessary to reach the rated calorific yield is the following one:
MAX
JUNIOR
MAJOR
MINOR

6. FLUE

Essential requirements for correct appliance operation:
• the internal section must preferably be circular;
• the appliance must be thermally insulated and impermeable and built with suitable materials which are resistant to heat, combustion
products and any condensation;
• there must be no narrowing and vertical passages with deviations must not be greater than 45°;
• if already used, it must be clean;
• the technical data from the instruction manual must be respected;
If the flues are of a square or rectangular section, the internal edges must be rounded with a radius of not less than 20 mm.
For the rectangular section, the maximum ratio between the sides must be ≤ 1.5.
A section which is too small causes a reduction in draught. A minimum height of 4 m is advisable.
The following materials are FORBIDDEN and compromise the good operation of the appliance: asbestos cement, galvanised steel, rough
and porous internal surfaces.
The minimum section must be 4 dm
dm
(for example 25x25 cm) for appliances with a diameter of more than 200 mm.
2
The draught created by your flue must be sufficient but not excessive.
A section of the flue which is too large can present a volume which is too large to heat and therefore cause operating difficulties for the
appliance; to avoid this, it is necessary to intubate the appliance for its entire height. A section which is too small causes a reduction in
draught.
The flue must be at a suitably distance from flammable or combustible material using suitable insulation or an air space.
It is FORBIDDEN to pass system piping or air ducts inside the flue. It is also forbidden to create moveable or fixed openings on the flue
itself, for the connection of further different appliances (See chapter CONNECTING A FIREPLACE OR OPEN HEARTH TO THE FLUE).
6.1.

CHIMNEY POT

The flue draught depends on the suitability of the chimney pot.
It is therefore essential that, if built in a handcrafted way, the exit section is more than twice the internal section of the flue
(Picture 2 at page
39) .
As it must always go past the ridge of the roof, the chimney pot must ensure exhaust even in the presence of wind
The chimney pot must meet the following requirements:
• Have an internal section equivalent to that of the chimney.
• Have a useful exit section of double the internal section of the flue.
• Be built so as to prevent rain, snow or any foreign body entering the flue.
• Be easy to inspect, for any maintenance and cleaning operations.
6.2.

CONNECTION TO THE CHIMNEY

Products with automatic door closing (type 1) must operate, for safety reasons, with the furnace door closed (except during the fuel loading
or ash removal phases).
Products with non-automatic door closing (type 2) must be connected to their own flue.
Operation with doors open is only allowed when supervised.
1191057 - IT - EN - DE - FR
(Picture 6 at page
42)
(Picture 6 at page
42)
Fuel
PRIMARY air
Wood
Wood
Wood
Wood
Picture 1 at page 39
shows some example solutions.
(for example 20x20 cm) for appliances whose pipe dimensions are less than 200 mm, or 6.25
2

SECONDARY air

CLOSED
PRE-ADJUSTED
CLOSED
PRE-ADJUSTED
OPEN 5 mm
OPEN 19 mm
OPEN 4 mm
OPEN 19 mm
TERTIARY AIR
/
/
/
/
(Picture 3 at page
40).
17

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Major - minor

Table des Matières