NETWORK MANAGEMENT CARD
Shutdown settings - Master
------------------------------------------------------------------------
1 : Name [Master]
2 : Shutdown if remaining time under (sec) [180]
3 : Shutdown if capacity under (%) [20]
4 : Shutdown timer enabled (0=No, 1=Yes) [0]
5 : Shutdown timer (sec) [1800]
6 : Shutdown duration (sec) [120]
7 : Restart if capacity exceed (%) [0]
0 : Exit
------------------------------------------------------------------------
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Shutdown settings – Outlet 1
------------------------------------------------------------------------
1 : Name [Group1]
2 : Switch off after (sec) [2147483647]
3 : Switch off if capacity under (%) [0]
4 : Shutdown duration (sec) [120]
5 : Switch on after (sec) [0]
0 : Exit
------------------------------------------------------------------------

6.3.8 Access Control menu

Ce menu est utilisé pour visualiser et modifier les paramètres d'accès à la carte.
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Access settings
------------------------------------------------------------------------
1 : New Login [MyName]
(1)
2 : Password [***********]
3 : Security Mode (1=conf., 2=full auth., 3=full auth. & SSL) [1]
4 : Telnet access enabled (0=No, 1=Yes) [1]
5 : Telnet security enabled (0=No, 1=Yes) [0]
6 : Console interface (Menu, CLI) [Menu]
0 : Exit
----------------------------------------------------------------------
(1) Ecriture-seule et crypté
(2) Lecture-écriture ou lecture seule selon la valeur du paramètre "Telnet access enabled".