6 Troubleshooting

All work on electrical parts or electrical connections and the refrigerant circuit must
be carried out by qualified and authorised personnel.
Warning: Disconnect electrical power before performing any operations on electrical
parts or on electrical connections.
Defect
The refrigerator does not
cool, the compressor will
not start.
The compressor only
performs brief attempts at
starting up.
The compressor functions
but doesn't cool.
The compressor runs for
a long time but doesn't
cool properly (reduced
efficiency).
Possible cause
No electrical power. Battery
in poor conditions. Faulty
thermostat. Defective
electronic control unit.
There is insufficient voltage or
else a drop in voltage during
the attempt to start. The
protection device is activated.
The Batteries are drained.
Loss of refrigerant through
the evaporator or the tubing.
Tubing clogged.
Insufficient ventilation,
the condensation unit is
overheating. The fan is not
working properly. There is too
much frost on the evaporator.
The door does not close
properly and lets in warm,
moist air. The condenser is
blocked by dust.
Intervention
Check to make sure that the electronic
control unit is receiving sufficient power
and voltage; check the fuse. Verify that the
internal lighting is working and that the
compressor is receiving power. Check the
cables, lugs and connectors. Verify that
the battery is charging properly. Check the
thermostat: Bridge T - C with a separate
cable. If the compressor will not start,
its electronics are probably defective.
Replace. If the compressor starts up with
the bridge, the thermostat is defective.
Replace the thermostat.
Check the cables and connections; remove
any traces of oxidation or corrosion.
Charge the batteries, start the motor or
connect the battery charger.
Carry out a leak check and repair any
leaks, drain and refill the proper amount of
R134a refrigerant. (This operation must be
carried out by a qualified technician.)
Increase the ventilation. Replace the fan.
Defrost the unit. Correct the position of
the door and check the gasket. Clean the
condensing unit.
61