Télécharger Imprimer la page

Setting An Additional Heater (Optional E-Heater); Setting The Installation Of The Remote Room Temperature Probe (Ambient Sensor) - Olimpia splendid SHERPA MONOBLOC S1 E 6 Mode D'emploi Et D'entretien

Publicité

Les langues disponibles
  • FR

Les langues disponibles

7.9.

Setting an additional heater (Optional E-heater)

After accessing the "Optional E-heater" function, you can
activate or deactivate any additional electric heater. This
heater may be single-stage or dual-stage (in the case of a
dual-stage model, you can decide whether or not to use
both stages by specifying the number of heaters in the
first parameter). You can also set the outdoor temperature
threshold below which it will be activated in place of the
heat pump. WARNING: to ensure the maximum energy
savings, you are advised to use "Logic 1". Press the top
right button to save the data entered.
NOTES:
1.
Once this function has been activated, it will give consent for the enabling of the additional electric
heaters (via a 230V~50Hz signal to the terminals indicated as "KM1" and "KM2"; if you use a single
heater, use the "KM1" terminals only) if the outdoor temperature falls below the value specified in the
"T-Eheater" parameter or if "Emergen. mode" is activated.
2.
The supplementary water probe must be installed downstream of the electric heater (for more infor-
mation, refer to the installation manual).
3.
If this function is used, no additional heat source can be enabled (Other thermal).
4.
Logic 2 is not available.
5.
The electric heater must be installed downstream of the 3-way valve (terminal side of the system).
6.
The DHW request will be met by the electric heater in the water tank (If present).
7.
If the relative function is activated (paragraph 8.3), the value of these parameters will be stored in the
memory and automatically reset after any possible voltage failure.
7.10.

Setting the installation of the remote room temperature probe (Ambient sensor)

After accessing the "Ambient sensor" function, you
can specify whether or not to enable the remote room
temperature probe (for more information about this
component, refer to the installation manual). Select
the required logic, then press "OK" to confirm.
NOTES:
1.
The "T-remote room" option in the "Ctrl.state" function will only be available if the room temperature
sensor is enabled.
2.
If the relative function is activated (paragraph 8.3), the value of these parameters will be stored in the
memory and automatically reset after any possible voltage failure.
Optional E Heater
Optional E Heater: 1
T Heater: -15°C
Logic 1
Remote sensor
Without
With
OK
Cancel
29

Publicité

loading