Télécharger Imprimer la page

LEGRAND Wattstopper LMCP8 Instructions D'installation page 2

Publicité

Les langues disponibles

Les langues disponibles

The LMCP series panel provides simple network-capable lighting control enabling the automation of lighting functions throughout an
entire facility.
The HDR relays in the panel can respond directly to inputs from Digital Lighting Management (DLM) switches, occupancy sensors,
daylight sensors, and input modules.
Relays in each LMCP panel can be assigned to up to 99 automation groups in any combination. There are 99 groups per panel, 254
schedules per panel and 32 dark/light per panel. Photocell operations are set up via an LMCT-100 handheld configuration tool. A group
can also respond to schedules sent from a BACnet-enabled building automation system (BAS). Individual relays, or groups of relays,
can also be controlled by DLM digital switches, occupancy sensors, LMLS series daylight sensors, and LMIO series input modules. DLM
devices are assigned to relays using Push n' Learn directly from the user input device, or via an LMCT-100.
Multiple panels may be networked together for global control operation without the use of a BAS. The LMCP panel also provides a
native-BACnet integration solution via BACnet MS/TP. Relay, group, and control device status, including occupancy sensor status, are
available as BACnet objects.
LMCP panels provide effective, code-compliant control of building exterior lighting as well as larger interior areas to provide centralized
control for the panels. Recommended applications include office building lobbies, corridors, loading docks, etc., as well as school
gymnasiums, commons areas and hallways. LMCP panels are also ideal for retrofit scenarios where mounting control equipment near
existing branch circuit breakers is beneficial and digital switch and sensor devices and load parameter configurability are required to
meet complex operational sequences.
Before installing the LMCP, read the instructions completely. For any questions, call our Technical Support team at:
800.879.8585.
Important Installation Notices
• All power must be turned OFF prior to wiring, installation or service.
• More than one disconnect may be required to de-energize power to the LMCP.
• External circuit protection to the LMCP is required (e.g., circuit breaker).
• Installation shall be in accordance with all applicable regulations, wiring practices, and codes.
• Care should be taken not to mix Class I and Class II wires.
• Do not energize wiring until the unit is fully assembled and connected circuits have been tested and found to be free of electrical
shorts.
• The LMCP is ESD sensitive. Observe precautions.
INTERIOR
DESCRIPTION AND OPERATION
CAUTION
THE DB9 CABLES CANNOT BE
PLUGGED IN OR UNPLUGGED
WITHOUT POWERING DOWN THE PANEL.
Figure 1: Panel interior
and enclosures
2
ENCLOSURES

Publicité

loading

Ce manuel est également adapté pour:

Wattstopper lmcp24Wattstopper lmcp48