* Table 1 Programs
1:60 Execution Interval (seconds)
Activation du multiplexeur
1:Do (P86)
1: 41
Set high Port1
2: Excitation et délai (P22)
01: 1
Ex Channel
02: 0
Delay w/Ex (0.01 sec units)
03: 15
Delay after Ex (0.01 sec units)
04: 0
mV Excitation
Début de la boucle de mesure des jauges de contraintes
3:Beginning of Loop (P87)
01: 0
Delay
02: 10
Loop Count
Début de la boucle de mesure des jauges de contraintes
4:Do (P86)
1: 72
Pulse Port 2
Délai
5:Excitation with Delay (P22)
1: 1
Ex Channel
2: 0
Delay W/Ex (units = 0.01 sec)
3: 1
Delay After Ex (units = 0.01 sec)
4: 0
mV Excitation
Instruction de mesure de pont complet
6: Full Bridge (P6)
1: 1
Reps
2: 3
50 mV slow Range
3: 1
DIFF Channel
4: 1
Excite all reps w/EXchan 2
5: 5000 mV Excitation
6: 1--
Loc [STRAIN #1 ]
7: 1
Mult
8: 0
Offset
Fin de la boucle de mesure des jauges de contraintes
7: P95 End
Début de la boucle de mesure des potentiomètres
8:Beginning of Loop (P87)
1:
0
Delay
2:
6
Loop Count
9:Step Loop Index (P90)
1:
2
Step
Impulsion de l'horloge
10:Do (P86)
1:
72
Pulse Port 2