Gigaset elements S30851-H2517-R101 Notice D'utilisation Et De Montage page 28

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

SMOKE ALARM
INSTALLATION POSITION FOR INCLINED ROOFS
10cm
90 cm
50 cm
10cm
60 cm
28
elements smoke
FOR INCLINED OR POINTED ROOFS
For installation to inclined or pointed ceilings, and rooms with an
inclined ceiling, smoke alarms should be installed at least 10 cm
vertically underneath the highest point, and no more than 90 cm
horizontally from the highest point.
These distances also apply when multiple alarms are installed in
one room. Install individual smoke alarms at appropriate distances
from each other.
CEILING INSTALLATION
When i tting smoke alarms to the ceiling, keep a distance of at
least 50 cm from a wall.
ANGLED CEILING
In rooms having a ceiling at an angle greater than 7 degrees
(corresponds to a height dif erence of about 50 cm over 4 m),
smoke alarms should be positioned on the ceiling in the higher
part of the room.

Publicité

Table des Matières
loading

Table des Matières