TSTAT0406 & TSTAT0407
GENERIC AC TO FURNACE WIRING (REFER TO UNITS I/O MANUAL FOR SPECIFICS
REQUIRED
NOTES:
24 VAC HUM - GOES TO HUMIDIFIER, ENERGIZES ON A CALL FOR W
1 STAGE AC WITH 1 STAGE FURNACE
THERMOSTAT
FURNACE
C
C
W2
-
R
R
W1
W
H
24VAC HUM
O/B
Y2
Y1
Y
G
G
L
-
A+
B-
GND
OUTDOOR
OD
SENSOR
ID
GND
GENERIC HP TO FURNACE WIRING (REFER TO UNITS I/O MANUAL FOR SPECIFICS
REQUIRED
NOTES:
24 VAC HUM - GOES TO HUMIDIFIER, ENERGIES ON A CALL FOR W
H - CAN BE PROGRAMMED FOR HUM OR DEHUM FUNCTION. DEHUM MUST BE SELECTED WHEN CONNECTED TO DEHUM ON VARIABLE SPEED
FURNACE.
1 STAGE HP WITH 1 STAGE FURNACE
THERMOSTAT
FURNACE
C
C
W2
-
R
R
W1
W
H
24VAC HUM
O/B
Y2
Y1
Y
G
G
L
-
A+
B-
GND
OUTDOOR
OD
SENSOR
ID
GND
= VARIABLE SPEED (DEHUM)
AC WITH FANCOIL / PSC FURNACE + HUMIDIFIER
VARIABLE SPEED
FANCOIL/SPP
ONLY
THERMOSTAT
H
C
W1
H
N.O. RELAY
HUMIDIFIE
M
115v
NOTE: A separate 115v supply should be used.
International Comfort Products, LLC
OPTIONAL
1 STAGE AC WITH VARIABLE SPEED FURNACE
AC
THERMOSTAT
C
C
W2
-
R
W1
H
O/B
Y2
Y
Y1
G
L
L
-
A+
B-
GND
OD
ID
GND
OPTIONAL
1 STAGE HP WITH VARIABLE SPEED FURNACE
HP
THERMOSTAT
C
C
W2
-
R
W2
W1
H
O
O/B
Y2
Y
Y1
G
L
L
-
A+
B-
GND
OD
ID
GND
= REQUIRED
HP WITH FANCOIL + HUMIDIFIER
VARIABLE SPEED
FANCOIL ONLY
THERMOSTAT
C
O
H
N.C. RELAY
N.C. RELAY
HUMIDIFIER
M
115v
NOTE: A separate 115v supply should be used.
NOTE: When using a humidifier on a HP connect to hot water.
FURNACE
AC
C
C
W2
R
W1
DEHUM
24 VAC HUM
O
Y1
Y/Y2
Y
G
L
OUTDOOR
SENSOR
*8MPV* "C" SERIES OR NEWER
*9MPV* "D" SERIES OR NEWER
FURNACE
HP
C
C
W2
▬▬▬
R
R
W1
W2
DEHUM
24 VAC HUM
O
O
Y1
Y/Y2
Y
G
L
OUTDOOR
SENSOR
*8MPV* "C" SERIES OR NEWER
*9MPV* "D" SERIES OR NEWER
AC WITH VARIABLE SPEED FURNACE + HUMIDIFIER
THERMOSTAT
H
C
H
SPDT RELAY
HUMIDIFIE
M
115v
NOTE: A separate 115v supply should be used.
Page 24
2 STAGE AC WITH 2 STAGE VARIABLE SPEED
FURNACE
THERMOSTAT
C
W2
-
R
W1
H
O/B
Y2
Y1
G
L
-
A+
B-
GND
OD
ID
GND
*8MPV* "C" SERIES OR NEWER
*9MPV* "D" SERIES OR NEWER
2 STAGE HP WITH 2 STAGE VARIABLE SPEED
FURNACE
THERMOSTAT
C
W2
-
R
W1
H
O/B
Y2
Y1
G
L
-
A+
B-
GND
OD
ID
GND
*8MPV* "C" SERIES OR NEWER
*9MPV* "D" SERIES OR NEWER
HP WITH VARIABLE SPEED FURNACE + HUMIDIFIER
FURNACE
THERMOSTAT
C
C
24 VAC HUM
DEHUM
H
SPDT RELAY
HUMIDIFIE
M
115v
NOTE: A separate 115v supply should be used.
NOTE: When using a humidifier on a HP connect to hot water.
Sep 2008
48201530101F
FURNACE
AC
C
C
W2
▬▬▬ R
R
W1
DEHUM
24 VAC HUM
O
Y/Y2
Y2
Y1
Y1
G
L
OUTDOOR
SENSOR
FURNACE
HP
C
C
W2
▬▬▬ R
R
W1
W
2
DEHUM
24 VAC HUM
O
O
Y/Y2
Y2
Y1
Y
G
L
OUTDOOR
SENSOR
FURNACE
C
O
DEHUM