Delivery Scope; Safety Instructions; Ambient Conditions; Technical Specifications - Elektrotechnik Schabus GX-HS Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 12
GB
THANK YOU FOR YOUR CONFIDENCE!
In order to be able to constantly guarantee the product's optimum functionality and readiness
for operation as well as your safety, we have a request: Please thoroughly read this operating
instruction prior to the first use and observe all safety instructions! The operating instruction
is a component of this product. Keep this, so you can always refer to it.

DELIVERY SCOPE

1 control device
1 operating manual

SAFETY INSTRUCTIONS

General
Before you start mounting the device please read the operating instructions carefully.
The installation shall be performed by qualified personnel.
Packaging material is not a children´s toy. Keep it away from children!
Do not open the device. It does not contain parts you have to maintain.

Ambient conditions

The standards used to assess the product specify limit values for use in the living area,
business area and in small enterprises; the product has been intended for use in the following
operating environments:
Residential buildings/living areas such as houses, flats, rooms, etc. selling areas such as
shops, wholesale markets, etc.
Premises of small enterprises such as workshops, service centers, etc.
All areas of application characterize themselves by a connection to the public low voltage
mains.

TECHNICAL SPECIFICATIONS

Operating voltage:
Power consumption:
Relay contact:
Switching capacity relay:
Sensor connection:
Buzzer connection:
Operating temperature:
Protection type:
Dimensions (HxWxD):

APPROPRIATE USE

The GAS ALARM GX-HS is a gas warning device for various gases and can already deliver a
warning at a gas concentration that lies below life-threatening values. This monitoring system
is, therefore, in line with its purpose, set to a very high sensitivity. For each type of gas, a
suitable sensor must be used (for information on trigger levels and minimum concentration,
see the instructions for the sensor). The alarm signal on the device is optical (a buzzer can
be optionally connected to the device).
At the same time, two potential-free relays are connected in order to e.g. cut the gas supply
line with a magnetic cut-off valve to prevent any more gas from leaking in the event of a leak
in the gas line or gas furnace.The device may not be used in areas with a risk of explosion.
Another use of the device as described above is not authorized.
230 V AC (+/-10%) / 50-60 Hz
approx. 2 W (stand-by)
2 potential-free two-way contacts
max. 5 A / 230 V
1 (5 V)
9 – 15 V / 50 mA
-15°C / +40°C
IP 20
57x72x90 mm

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

300200

Table des Matières