Change of lighting time of
filter sign
According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.
Follow the basic operation procedure
1
2
3
4
5
6
(
).
3
For the CODE No. in Procedure
, specify [01].
4
For the SET DATA in Procedure
, select the
SET DATA of filter sign lighting time from the
following table.
SET DATA
Filter sign lighting time
0000
None
0001
150 H
0002
2500 H (Factory default)
0003
5000 H
0004
10000 H
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due
to installation place of the indoor unit or structure of
the room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.
Follow the basic operation procedure
1
2
3
4
5
6
(
).
3
For the CODE No. in Procedure
, specify [06].
4
For the SET DATA in Procedure
, select the
SET DATA of shift value of detection temperature
to be set up from the table below.
SET DATA
Detection temp shift value
0000
No shift
0001
1.8°F (+1°C)
0002
3.6°F (+2°C) (Factory default)
0003
5.4°F (+3°C)
0004
7.2°F (+4°C)
0005
9.0°F (+5°C)
0006
10.8°F (+6°C)
33-EN

Group control

(Group control operation)
In a group control, operation of maximum 8 indoor
units can be controlled by a remote controller.
Twin, triple or double twin of an outdoor unit is one of
the group controls.
The indoor unit connected with outdoor unit (Individual/
Header of twin) controls room temperature according
to setting on the remote controller.
<System example>
OUT
OUT
OUT
OUT
OUT
Header
IN
IN
IN
IN
IN
1-1
2-1
3-1
4-1
Max. 8 units
Remote
controller
1. Display range on remote controller
The setup range (Operation mode/Fan speed
select/Setup temp) of the indoor unit which was
set to the header unit is reflected on the remote
controller.
2. Address setup
If there is no serial communication between indoor
and outdoor when the power is turned on, it is
judged as follower unit of the twin. (Every time when
the power is turned on)
The judgment of header (wired) / follower (simple)
of twin is carried out every time. It is not stored in
nonvolatile memory.
Turn on power of the indoor unit to be controlled in
a group within 3 minutes after setting of automatic
address.
If power of the indoor unit is not turned on within 3
minutes (completion of automatic address setting),
the system is rebooted and the automatic address
setting will be judged again.
1) Connect indoor/outdoor connecting wire surely.
2) Check line address/indoor address/group
address of the unit one by one.
Especially in case of twin, triple, double twin,
check whether they are identical system address
or not.
3) The unit No. (line/indoor group address) which
have been set once keep the present status as
a rule if the unit No. is not duplicated with one of
another unit.
– 17 –
Remote controller sensor
The sensor temperature or operational status of
indoor unit, outdoor unit, or remote controller can be
monitored.
Monitor function
Code
Data
00
0024
Return
8-1
Procedure
1
Push the [
MENU] button to display the
menu screen.
2
Push and hold the [
the [
] button at the same time to
display the "Field setting menu".
→ Push and hold the buttons for more than 4
seconds.
3
Push the [
] / [
select "4. Monitor function" on the
"Field setting menu" screen, then push the
"
Set" [
F2] button.
[
]
[
→ Push the
/
the code to check data.
4
Push the [
CANCEL] button to return to
the "Field setting menu" screen.
Indoor unit data
Code
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
Indoor unit heat exchanger (coil)
03
Indoor unit heat exchanger (coil)
04
Indoor unit fan cumulative operating hours
F3
Indoor unit refrigerant leak detection sensor
E2
* Display and the contents
- - - - : Sensor function is not available.
0000 : Normal
0001 : Sensor has been used for 5 years.
0002 : Sensor trouble or exceeding the life of the
product for sensor
0003 : Sensor is detecting refrigerant leak
Outdoor unit data
MENU] button and
Code
Outdoor unit heat exchanger (coil)
60
61
Outside air temperature (TO)
62
Compressor discharge temperature (TD)
] button to
63
Compressor suction temperature (TS)
65
Heatsink temperature (THS)
6A
Operating current (x1/10)
Outdoor heat exchange (coil)
6D
]
button to select
Compressor cumulative operating hours
F1
Data name
temperature (TCJ)
temperature (TC)
(x1 h)
output*
Data name
temperature (TE)
temperature (TL)
(x100 h)
34-EN