on and off by the utility.
• The heater must not be located immediately below a
socket-outlet.
• Means for disconnection having a contact separation in
all poles must be incorporated in the fixed wiring in
accordance with the wiring rules.
• For correct installation on the wall, thanks to refer to
'Installation on wall' part.
• Fixed heaters are to be installed so that switches and
other controls cannot be touched by a person in the bath
or shower.
• Connect the two conductors and the pilot wire of the
supply cord to a connection box in respecting the
following polarities:
- Live: Brown
- Neutral: Blue
- Pilot wire: Black
• WARNING: In order to avoid overheating, do not cover
the heater.
Warning: this product shall be installed in the volume 2 or
hors volume only according to the national wiring rules (For
France NF C 15-100)
Note: The below drawing is for reference only.
We suggest you to contact a professional electrician for
assistance.
In the case as of buildings room, a room receiving a bath or
a shower and socket-outlets lower or equal to 32 A the
circuit corresponding must be protected by a device with
differential residual current (RCD) lower or equal to 30 mA.