EN
3-WAY VALVE KIT, ON/OFF MOTORIZATION
The 3-way valve kit, ON/OFF motorization, connected to the control panels of FWEC,
permits to set the room temperature by cutting off the water flow by means of the
heat exchanger.
The kit is available for all FWB/FWP unit models.
Code
Acronym Fan coil units
diameter
E2MV107A6
models from 02 to 10, ON/OFF 230V
The actuator is to be coupled to a control panel:
Control
assembly-type
Panel
FWEC
wall-mounting, microprocessor
As far as the coupling with the FWEC control is concerned, position the temperature
probe into the appropriate trap.
ON/OFF 230V VERSION
The kit comprises:
3-way valve / 4 connections with built-in by pass, made of brass, max. work pressure
16 bar:
Electro-thermal actuator having the following specifications:
- power supply: 230V
- activation: ON/OFF
- total opening time: 3 minutes
The flow resistance of the connecting valve/hydraulic kit assembly is
obtained from the following formula:
∆P
W
where
∆P
is the flow resistance expressed in kg/cm2
W
Q
is the water flow rate expressed in m
W
K
is the flow rate identified in the table
V
Valve
Kvs straight
3/4 "
INSTALLATION
1. The position of water input, connections to heat exchanger and water returning
to the circuit is shown in figure 1 according to the indications on the valve body.
A= heat exchanger water outlet
B= water inlet from circuit
C= water returning to circuit
D= heat exchanger water inlet
2. The
3-way valve kit, ON/OFF motorization, is to be installed before
E2MV107A6
powering on the unit.
WARNING:
Each unit requires a switch (IL) on the feeder line with a distance of at least 3 mm
between the opening contacts, and a suitable safety fuse (F).
The installer is in charge of carrying out the hatched connections.
3. Install the hydraulic unions as indicated in the diagrams of figures 2-7 that show
the following:
Figure 2: Assembly of kit
E2MV107A6
Figure 3: Assembly of kit
E2MV107A6
4. Connect valve wire to the terminal board on the electric box respecting the positions
specified.
5. Make the electrical connections of the control board following the indications of
the installation manual of FWB/FWP unit .
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
Type of
system
2- 4 pipes, 2 pipes+el. res.
= (Q
/ K
)
2
W
V
/h
3
Kv by-pass
2,8
1,8
- water connections on the left
- water connections on the right
INSTALLATION AND OPERATION MANUAL
2-WAY VALVE KIT, ON/OFF MOTORIZATION
The 2-way valve kit, ON/OFF motorization, connected to the control panels of FWEC,
permits to set the room temperature by cutting off the water flow by means of the
heat exchanger.
The kit is available for all FWB/FWP unit models.
Valves
Code
Acronym Fan coil units
diameter
3/4"
E2MV207A6
models from 02 to 10, ON/OFF 230V
The actuator is to be coupled to a control panel:
Control
assembly-type
Panel
FWEC
wall-mounting, microprocessor
As far as the coupling with the FWEC control is concerned, position the temperature
probe into the appropriate trap.
ON/OFF 230V VERSION
The kit comprises:
2-way valve with built-in by pass, made of brass, max. work pressure 16 bar:
Electro-thermal actuator having the following specifications:
- power supply: 230V
- activation: ON/OFF
- total opening time: 3 minutes
The flow resistance of the connecting valve/hydraulic kit assembly is
obtained from the following formula:
where
∆P
is the flow resistance expressed in kg/cm2
W
Q
is the water flow rate expressed in m
W
K
is the flow rate identified in the table
V
Valve
3/4 "
INSTALLATION
1. The position of water input, connections to heat exchanger and water returning
to the circuit is shown in figure 1 according to the indications on the valve body.
A= heat exchanger water outlet
B= water inlet from circuit
C= water returning to circuit
D= heat exchanger water inlet
2. The
2-way valve kit, ON/OFF motorization, is to be installed before
E2MV207A6
powering on the unit.
WARNING:
Each unit requires a switch (IL) on the feeder line with a distance of at least 3 mm
between the opening contacts, and a suitable safety fuse (F).
The installer is in charge of carrying out the hatched connections.
3. Install the hydraulic unions as indicated in the diagrams of figures 2-7 that show
the following:
Figure 2: Assembly of kit
Figure 3: Assembly of kit
4. Connect valve wire to the terminal board on the electric box respecting the positions
specified.
5. Make the electrical connections of the control board following the indications of
the installation manual of FWB/FWP unit .
3
Type of
system
2- 4 pipes, 2 pipes+el. res.
∆P
= (Q
/ K
)
2
W
W
V
3
/h
Kvs straight
Kv by-pass
2,8
- water connections on the left
E2MV207A6
- water connections on the right
E2MV207A6
Valves
3/4"
1,8
UT66002329-01