INIM Electronics Previdia 216 Manuel D'installation page 26

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 33
[A]
[B]
Mini USB port
Jumper connectors for enablement of the
[C]
ground-fault test
[D]
OUT1
[E]
OUT 2
[F]
RELAY
Relay - voltage free contact
The indications in brackets below terminals OUT1, OUT2 and RELAY [D, E, F] show the respective factory default settings.
IFM24160 LED
CAN
ON
MAINS
BATT
Maximum current draw from mains
Maximum output ripple
Maximum available current
Imax a (as per EN54-4)
Imax b (as per EN54-4)
Maximum voltage charge adapted to temperature
Maximum internal resistance of battery
Battery shutdown voltage
Operating temperature
26
Status LED
Supervised output
Colour
Blue
Green
Module operating normally
Yellow
Mains failure fault
Yellow
Battery inefficiency or fault
IFM24160 module - technical specifications
Power supply voltage
Output voltage
Imin
Batteries
Battery charger
(Ri Max)
Figure 2 - IFM24160
[G]
[H]
L N
[I]
Hole for the grounding bar screw and for the wire with the
[J]
Input voltage
[K]
selector
[L]
On solid
Activity on the CAN communication BUS
Fire detection control panel
Battery connector
AC Mains input terminals
Hole for the grounding bar screw
and for the earth conductor
eyelet terminal
CAN drive connector (opposite)
Flashing
Slow flashing: overload (system voltage draw is
excessive)
Fast flashing: PSU unit overheated
Fast flashing: system ground fault
230V~ (+10% - 15%)
115V~ (+10% - 15%)
50/60 Hz
1.1A @ 230V
2A @ 115V
27.6 V
nominal
20 - 27.6 V
1%
5.2A
4A
4A
185mA
2 x 12 V 24Ah, NPL24-12I or
2 x 12 V 17 Ah, NP 17 -12-FR or equivalent
with UL94-V1 flame class enclosure or higher
1.2A
1Ohm
19.5V
from -5°C to +40°C
230/115 V
Description of the parts

Publicité

Table des Matières
loading

Table des Matières