1.4. Temperature sensor installation

The air supply temperature sensor B1 (Fig. 1.4a) must be installed in the air supply duct after cooler section (if
not, then after heater). The minimal distance from the duct connection of the unit up to the sensor be not less
than two circular connection diameters. The water temperature sensor B5 (Fig. 1.4 b.) is mounted on the return
water pipe, by screwing it into the provided hole. The sensor must be thermally insulated!
Supply air temperature sensor B1
Water temperature sensor B5
Fig. 1.4 b
Fig. 1.4 a
B1
+
B
≥ 5D

2. OPERATING MANUAL

2.1. Unit control with the control panel

The air handling unit can be operated by one of the following panels (Fig. 2.1).
C6.1 – panel with a touch screen for parameters of air handling unit setting and indication. The panel has inte-
grated thermometer and hygrometer for indoor climate monitoring.
C6.2 – panel with touch-sensitive buttons is intended for main air handling unit parameters setting.
C6.1
C6.2
Fig. 2.1. Choice of control panels
22
UAB AMALVA we reserve the right to make changes without prior notice
C6-17-01