Balancing The Circuits - emmeti TM3 Mixing Unit Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3. BalaNCINg aND SETTINg THE SYSTEM

3.3 Balancing the circuits

3.3.1 Adjusting the lockshields (where applicable)
Fig. E
Proceed as follows to adjust them:
– Remove cap .
– Turn the cap upside down and, with its cavity manually turn (Fig. E) the
lockshield  until it is fully open, 4 turns max.
– Use a CH 4 hex spanner to tighten regulator  (Fig. F).
The lockshield is now ready to be set up:
– Loosen regulator  by the desired number of turns.
– Insert the cap again.
The cap can also be lead sealed in position using the holes in the
flaps  to secure it directly to the manifold, thereby preventing any
tampering.
12
Fig. F
Pressure drops
(Valve* + Lockshield)
1000
100
10
10
Portata / Flow rate / Caudal / Débit / Durchflussmenge / Portata / Расход
Q [l/h]
= No. of turns to open the flow-rate meter.
∆p = supply + return
TA: Fully open.
* Valve fully open
Kv values at different openings
(Valve* + Lockshield)
1,2
1
0,8
0,6
0,4
0,2
0
0
0,5
1
TA: Fully open.
The above values are obtained with water at 15°C
* Valve fully open
GB
GB
0
Kv=0,05
0,5
Kv=0,10
1
Kv=0,26
1,5
kv=0,45
2
Kv=0,72
2,5
Kv=0,98
T.A.
Kv=1,07
100
1000
(l/ h)
2,5 TA
1,5
2

Publicité

Table des Matières
loading

Produits Connexes pour emmeti TM3 Mixing Unit

Table des Matières