Technical Data; General Data And Operating Conditions - Lenze 9300 Série Instructions De Montage

Table des Matières

Publicité

3

Technical data

3.1

General data and operating conditions

General data
Conformity and approval
Conformity
CE
Approbation
UL
Protection of persons and equipment
Type of protection
Earth leakage current
Insulation of control
circuits
Insulation resistance
Protective measures
EMC
Noise emission
Interference immunity
EDKVS9332X DE/EN/FR 4.0
General data and operating conditions
2006/95/EC
Low−Voltage Directive
2004/108/EG
EMV Directive
UL 508C
Industrial Control Equipment
File No. E132659
for USA and Canada
EN 60529
IP20
IP41 on the heatsink side for thermally separated mounting
(push−through technique).
NEMA 250
Protection against contact in accordance with type 1
IEC/EN 61800−5−1
> 3.5 mA
EN 61800−5−1
Safe mains isolation by double (reinforced) insulation for
terminals X1 and X5.
Basic insulation (single isolating distance) for terminals X3,
X4, X6, X7, X8, X9, X10 and X11.
IEC/EN 61800−5−1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
Against short circuit, earth fault (earth−fault protected during
mains connection, limited earth−fault protection during
operation), overvoltage, motor overtemperature (input for
PTC or thermal contact)
IEC/EN 61800−3
Cable−guided, up to 10 m motor cable length with mains
filter A: category C2.
Radiation, with mains filter A and installation in control
cabinet: category C2
IEC/EN 61800−3
Category C3
l
Technical data
Observe stipulations and safety
instructions!
3