6.6 Calibrage de l'entrée
Attention : cette procédure doit être effectuée par du personnel qualifié.
Wait for more than 10 sec.
ON
S/C
H.B.
Type 30250
START TUNE
UNIT OFF
Mantain Kay CAL pushed
and Switch ON
Release key
when red and yellow
led are ON
Yello and red leds
are flashing
SSR
INPUT TYPE
from start flashing
yellow and red leds
The leds will
stop flashing
SSR input (3-30V)
is tuned
END
TUNE
Manuel d'Utilisation 75A à 700A
2sec.
ON
S/C
H.B.
ON
S/C
H.B.
ANALOG
Within 10 sec. from start
flashing yellow and red leds
push again momentary
CAL Key
Yellow led only is
flashing, apply
0 input Signal
I.E.: 0V for 0-10V
4mA for 4-20mA
Now press CAL Key again
Red led only is
flashing, apply
10V for 0-10V input
or
20mA for 4-20mA input
Now press CAL Key again
Analog input
is tuned