Instellen Luchtcapaciteit - Vasco SYSTEM C Manuel D'installation Et D'utilisation

De l'unité de ventilation capteur hygrométrique intégré à l'unité
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operation
instructions
VMI-02MP03
A
5
B
4
C
3
A: Status LED
A: Status LED
B: Mode LEDs
B: Mode LEDs
1
About this manual
C: Touch Button
1.1 About the device
The VMI-02MP03 is a presence sensor for a ventilation system. The device
communicates information about presence via wireless communications with
the central control device.
1.2 How to use this manual
3
This manual is intended as a reference book by which qualified installers can
4
5
install the VMI-02MP03 (henceforth called "device") and users can use the device
INBEDRIJFSTELLING
for its intended purpose. Make sure you have read and understood the manual
before you install and/or use the device.
EN INREGELING
1.3 Original instructions
The original instructions for this manual have been written in English. Other
language versions of this manual are a translation of the original instructions.
1.4 Admonitions
NOTE
'Note' is used to highlight additional information.
2
Safety
2.1 Directives
Hereby Honeywell declares that this VMI-02MP03 is in compliance with the
e
ro
• EMC directive: 2014/30/EU
• Low voltage directive: 2014/35/EU
• RED directive: 2014/53/EU
• R0Hs directive: 2002/95/EC
• WEEE directive: 2002/96/EC
2.2 Signs on the unit
CE marking of conformity
Dispose according to European Community
Directive 2002/96/EC (WEEE).
2.3 General safety instructions
The device is designed for indoor use only. Do not expose the device to rain or
moisture, to avoid short circuit. Short circuit may cause fire or electric shock haz-
ard. Operate the device between 0°C and 40°C. For cleaning of the device use a
soft damp cloth only. Never use any abrasive or chemical cleaner.
Do not paint the device.
3
Description
3.1 Intended use
Instellingen:
The device is designed for following purposes:
3
4
1 Detect the presence of a person.
2 To switch a device, like a lamp, in case of presence.
Every other or further use is not in conformance with the intended use.
ventilatorstand
Capaciteit [m³/h]
Druk [Pa]
Spanning [V]
Vermogen [W]
3.2 Working principle
The device communicates with the control device using wireless communica-
tions in order to control the ventilation. The device switches on the light if it
detects movement. Movement in front of the device requests the high fan
BEDIENING SCHAKELAARS
speed and switches light on.
Zie pagina 2.
3.2.1 Light switch
The device detects movement in front of the device. If movement is detected,
it switches the lights on for the relay on time (ROT) and sets the ventilation to
high for a time, depending the ventilation unit.
INGEBRUIKNAME Bewegingssensor PIR (11VE20021)
4
4.1 Show status
Aanmelden: Maak de ventilatie-unit kort spanningsloos door de stekker uit het
1
1 Tap the button.
The Status LED shows the status of the system.
stopcontact te nemen en plaats deze weer terug. Hierna zal de ventilatie-unit
After 2 seconds the LED indicates detection of movement.
2
gedurende 10 minuten nieuwe schakelaars zoeken. Sluit de voedingskabel van
5
de bewegingssensor aan. Alle LED's gaan gedurende 3 seconden oplichten. Na
5.1 Preparation
3 seconden zal de status LED groen oplichten. De groene LED zal na 2 seconden
knipperen bij detectie van beweging. Houdt nu de bedieningszone voor 10 secon-
C: Touch Button
den in. Wanneer de status LED tussen groen en rood flikkert kunt u het bedienings-
5.2 Installation procedure
paneel loslaten. Indien de koppeling succesvol was zal de status LED kortstondig
groen flikkeren. Wanneer de status LED kortstondig rood flikkert was de koppeling
onsuccesvol en zal het aanmeldproces opnieuw doorlopen moeten worden.
6
7
Indien alle luchttechnische en elektrische aansluitingen uitgevoerd zijn mag de
stekker in het stopcontact gestoken worden.
Instellen van de luchtcapaciteit:
Het debiet in stand HIGH kan ingesteld worden door middel van de poten-
tiometer. De potentiometer bevindt zicht op de printplaat. Het debiet van
stand "HIGH" kan ingesteld worden door met een platte schroevendraaier de
potentiometer te roteren. Als deze volledig in tegenwijzerzin is gedraaid, is de
ventilatie-unit op zijn minimum ingesteld. Als de deze volledig in wijzerzin is
gedraaid is de ventilatie-unit op zijn maximum ingesteld. Het maximum van
de unit komt overeen met 400m³/h bij 150Pa. Onderstaande figuur geeft een
richtwaarde voor het instellen van de potentiometer.
200 m
/h
3
100 m
/h
3
MIN
1
100
15
230
4,6
Operation
Installation
DANGER
Disconnect power at supply line, circuit breaker or fuse before installing the
device.
NOTE
Do not place the device in a metal casing.
A
8
F
X
A
B
E
C
B
C
D
N L
20W
Max
300 m
/h
3
VMI-02MP03
E
H5V4 1823
T40
230VAC 50Hz 5mA IP21
400 m
/h
3
F
: 230V switch, suitable for 20W resistive load.
Not all
have
else not
11VE00004
C400
Basic RF
2
3
1
200
400
100
40
150
15
230
230
230
11,4
58,8
4,8
INSTALLATIEHANDLEIDING VOOR DE INSTALLATEUR
N
N
L
11VE0034
C400
FANBOX C400
Basic RF LE
2
3
1
200
400
100
40
150
15
230
230
230
11,6
60,3
4,8
NL
FR
11VE00036
Basic RF LE
2
3
200
400
40
150
230
230
11,6
60,3
13