1 Preface
Thank you for using a Nederman product!
The Nederman Group is a world-leading supplier and
developer of products and solutions for the environ-
mental technology sector. Our innovative products
will filter, clean and recycle in the most demanding of
environments. Nederman's products and solutions will
help you improve your productivity, reduce costs and
also reduce the impact on the environment from in-
dustrial processes.
Read all product documentation and the product iden-
tification plate carefully before installation, use, and
service of this product. Replace documentation imme-
diately if lost. Nederman reserves the right, without
previous notice, to modify and improve its products
including documentation.
This product is designed to meet the requirements
of relevant EC directives. To maintain this status, all
installation, maintenance, and repair is to be done
by qualified personnel using only Nederman original
spare parts and accessories. Contact the nearest au-
thorized distributor or Nederman for advice on tech-
nical service and obtaining spare parts. If there are
any damaged or missing parts when the product is de-
livered, notify the carrier and the local Nederman rep-
resentative immediately.
2 Safety
2.1 Classification of important informa-
tion
This document contains important information that
is presented either as a warning, caution or note, ac-
cording to the following examples:
WARNING! Risk of personal injury
Warnings indicate a potential hazard to the
health and safety of personnel, and how that
hazard may be avoided.
CAUTION! Risk of equipment damage
Cautions indicate a potential hazard to the
product but not to personnel, and how that
hazard may be avoided.
Notes contain other information that is import-
ant for personnel.
2.2 General safety instructions
WARNING! Risk of personal injury
Only properly trained personnel are allowed to
open, install, use and service this product.
HV Control Panel
Table 2.1 Explanation of sign and sticker sym-
bols used on the product components or with
documentation.
Sign
3 Description
3.1 Intended use
HV Control Panel is intended for the control and su-
pervision of a high vacuum system with Nederman
FlexFilter, and VAC or RBU vacuum source.
For FlexFilter EX, use the HV Control Panel EX.
3.2 Function
The function of the HV Control Panel is to control
cleaning, and if applicable, emptying Nederman Flex-
Filter and pre separators.
It starts a VAC or RBU using the Star/Delta (Y/D) meth-
od in order to reduce starting motor current. During
the start sequence, the startup valve in the vacuum
unit reduces the motor load. When in Delta (D) mode,
the valve is activated and the unit can supply the sys-
tem.
There are three control modes: Off, Standby, and Run-
ning.
The control panel has also a week timer and an over-
time/timer function.
A Pilot signal (PS) is used in installations with auto-
matic start/stop controlled by microswitches on work
sites (AS-set).
After power-on, the control panel is normally in Off
mode and can be set to Standby mode either by press-
ing the green Start button or remotely.
The control panel enters Standby mode and waits for
a pilot signal. When the pilot signal becomes active,
the control panel goes into Running mode and the
VAC/RBU starts. A test start can be done by pressing
the Test-start button.
When the Pilot Signal becomes deactivated, the SSR
stop delay begins to count down until the VAC/RBU
stops and the HV Control Panel goes into Standby
mode.
When RBU is selected, the DIR idling delay also starts
to count down, the startup valve opens and the RBU
goes into Idling mode.

Description

Risk of electric shock. Even when
the main switch is turned off to the
product, there is still be electricity
in the cabinet. There may also be
control signals with an external
supply.
EN