TIB-REM Redundancy/Parallel Module
This module ensures that a redundancy function is maintained. Even when one of the connected input power supplies
becomes faulty, with internal short circuit – the output voltage of the system is maintained by the remaining power
supply. Additionally, an active power sharing function ensures that both input power supplies are loaded equally.
Input Voltage
Order Code
TIB-REM480
11-56VDC
Electrical Specification
Operational Input voltage range
Internal voltage drop (Vin1=Vin2)
Input Voltage Compensation Range
Input current
Nominal output current
Output boost current
Short circuit protection
Standby Power
Typical Power Loss
Operating Ambient Temperature
Storage ambient Temperature
Output Power Derating
Transient voltage
Protection Class
Degree of Protection
Humidity
Maximum altitude
Connections: Input
Wire Size:
The required cross section of the wires should be established by electrician, depending on the maximum current ratings
The required cross section of the wires should be established by electrician, depending on the maximum current ratings
 External power supplies must be fully stabilised (SELV) and should be of the same ratings.
Leave a free space of minimum 50mm (2in.) above and below the power supplies and isolation module.
 Observe the indication on the LEDs. If the balance OK LED is ON - no voltage adjustment is necessary. Otherwise, for best
power sharing, adjust the voltage of individual power supply with the isolated screwdriver. After adjustments, the output
voltages should be within ±0.10V. This will be indicated by the balance LED
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment might be
impaired.
 Recycling: The unit contains elements that are suitable for recycling, and components that need special disposal. You are
therefore requested to make sure that the device will be recycled environment friendly at the end of its service life.
http://www.tracopower.com
Output DC Current
range
Nominal
40A
40A max (continuous)
60A/4s max
Provided by power supplies: TIB 080-112, TIB 080-124, TIB 080-148,
TIB 120-112, TIB 120-124, TIB 120-148, TIB 240-124, TIB 240-148,
TIB 480-124, TIB 480-148
1.5W max
6W max at 40A output current
-20°C to +70 °C
-25°C to +80 °C
2%/K above 60 °C
OVC II; 2500Vpeak
Class III
IP20
5-95%, no condensation
2000m
2 x 2 Screw type terminal Combi – Type. Recommended tightening torque 0.6Nm
4 Screw type terminal Combi – Typ. Recommended tightening torque 0.5 to 0.6Nm
Input & Output 1.5mm
Output DC Current
Boost
60A (4s)
11Vdc min. - 56Vdc max. (fully stabilized SELV)
0-0.2V (2x20A) typ.
Parallel Operation
Each Power Supply
2
2
– 4.0mm
[AWG 16 – AWG 10]
Voltage drop across the
diodes/internal losses
0-0.2V
±0.20V max
20A max (continuous)
Rev:4.0/ 4625
loading

Sommaire des Matières pour TRACO POWER TIB-REM480

  • Page 1 Output DC Current Output DC Current Voltage drop across the Order Code range Nominal Boost diodes/internal losses TIB-REM480 11-56VDC 60A (4s) 0-0.2V Electrical Specification Operational Input voltage range 11Vdc min. - 56Vdc max. (fully stabilized SELV) Internal voltage drop (Vin1=Vin2) 0-0.2V (2x20A) typ.