The following components and table apply up to serial number BR2018-H-00025:
• Length of drain hose 500mm
• Drain hose Ø = 15mm
• Knee on drain instead of wire spring clamp
• Alarm and alarm table:
Alarm LED
Alarm LED flashes
Alarm LED
continuously on
Alarm LED
continuously on
Alarm LED
continuously on
Alarm LED
continuously on
Service LED
continuously on
Power LED flashes
¹ See chapter 10 for version adjustment
Section 10 – Version adjustment
Meaning
No airflow
Contact with SHC80
sensor broken
No water supply
Heating faulty
T3 sensor outside air
faulty
The cassette must be
replaced
There is no
communication between
optional controller and
humidifier
Action
Check that the HRV unit fan is moving air.
Check SHC80 wiring and if necessary repair, check that
the light on SCH80 sensor flashes regularly, if not
replace faulty sensor.
- Check if the water tap is open.
If the tap is open and there is a demand (outside
temperature below 12 ° C) check the strainer in the
connection coupling, it must be clean.
- Check the functioning of the water valve. Disconnect
the black supply hose from the knee on the unit, and
reset the unit by plugging out and plugging in again; if
water comes out and the water valve and this stops after
90sec, then the valve is OK, the water keeps flowing or
no water comes out of the hose, then the water valve is
defective, replace the water valve. If the water valve
works and the matrix does not get wet after the valve has
switched, the legionella filter is clogged; replace the
cassette.
If the matrix does get wet and still has an alarm, the
matrix is contaminated and the cassette must be
replaced. Product No .: 351025
Check air temperature after the humidifier, this must be
>17ºC, if not air heater is faulty. Call installer for
replacement.
Check wiring for break or wear, in case of doubt replace.
Testing can be done by keeping the sensor at 8°C or
colder in water or air; the Evap must then be activated
because the water valve opens.
To be able to humidify safely it is necessary to replace
the complete cassette; Order product code 351025 from
your dealer.
In the interim, you can
reset the service alarm at
the bottom by pressing and
holding the reset button
for 30 seconds. The
opening is located next to
the service LED.
ATTENTION the LegioSafe filter will soon become
obstructed, after which proper and safe operation is no
longer guaranteed!!
Check status of the batteries on controller. If necessary
replace (4xAAA).
Reduce distance between the Evap module and the
controller if WIFI symbol is not visible, press (MODE)
button to restore and test connection.
Evap
12