Surface Mount Pedestals
OP5BK18, OP5GY18, OP5BK24, OP5GY24,
OP2BK18, OP2GY18, OP2BK24, OP2GY24
SAFETY SECTION
Warning
TO AVOID FIRE, SHOCK OR DEATH
• TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST POWER
BEFORE WIRING
Warning
TO BE INSTALLED AND/OR USED WITH ALL APPLICABLE LOCAL ELECTRICAL
CODES AND REGULATIONS.
PRODUCT INSTALLATION
The Service Mount Pedestals are Type 3R Enclosure. At installation, do not fasten conduits, raceways or cables to the pedestal. Form "S"
loops with the cables and wires to prevent stress on the wires inside the enclosure. This ensures that the cables and wires have adequate
room to adjust for grade level changes caused by freeziing and thawing cycles, and soil subsidence. Ground wires are included with the
supply conductors, and can be used to provide the connection to the pedestal's ground terminal. Single-Gang pedestals intended only
for use with cULus Listed (KCXS/7) GFCI receptacles rated at 20 A max. Double-Gang
pedestals are intended only for use with cULus Listed (KCXS/7) GFCI receptacles rated
at 20 A max., cULus Listed (RTRT/7) receptacles rated at 60 A max., or cULus Listed
(WFXV/7) switches rated at 60 A max.
Installed devices rated at 15-20 A must be weather-resistant (cover provides in-use
protection) and devices rated at 30-60 A must be water-tight.
The pedestals are also UL listed as mounting post. There are no knockout locations
provided. Mounting holes for fixtures or photocells must be drilled before installation.
When fixtures are mounted or raceways are extended from the top of the pedestal, a
conduit hub, sealing locknut, or sealing washer must be used.
These models can accommodate two 1-1/2" conduit raceways. There are four (7/16")
holes on the pedestal base, which are secured to a concrete surface with the provided
hardware, anchors, washers and acorn nuts.
Wire Size (AWG) Copper Only
10-14
8
4-6
This warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased or (b) completing a
warranty claim online at www.intermatic.com. This warranty is made by: Intermatic Incorporated, Customer Service 1950 Innovation Way,
Suite 300, Libertyville, IL 60048. For warranty service go to: http://www.Intermatic.com or call 815-675-7000.
Torque (lb - in.)
20
25
35
TWO-YEAR LIMITED WARRANTY
Caution
SPLICES MUST BE MADE WITH PROPER SPLICING EQUIPMENT, MATERIALS
OR KITS
Caution
NO USER SERVICABLE COMPONENTS. DO NOT ATTEMPT TO SERVICE OR
REPAIR
Caution
USE COPPER CONDUCTORS ONLY
SCALE 1 : 2
Single Gang Models
Base Measurement
4.75
4.75
.44 4X
.44 4X
4.75
4.75
2.84
2.84
4.84
4.84
SCALE 1 : 2
Double Gang Models
Base Measurement
6.75
6.75
4.84
4.84
6.75
4.84
6.75
4.84
.44 4X
.44 4X
loading

Sommaire des Matières pour Intermatic OP5BK18

  • Page 1 This warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased or (b) completing a warranty claim online at www.intermatic.com. This warranty is made by: Intermatic Incorporated, Customer Service 1950 Innovation Way,...
  • Page 2 Ce service de garantie est disponible (a) en retournant le produit au vendeur auprès duquel l’unité a été achetée ou (b) en remplissant un formulaire en ligne de réclamation de garantie sur www.intermatic.com. La présente garantie est offerte par : Intermatic Incorporated, Customer Service, 1950 Innovation Way, Suite 300, Libertyville, IL 60048, États-Unis.
  • Page 3 Este servicio de garantía está disponible mediante (a) la devolución del producto al proveedor al que se le compró la unidad; o (b) el llenado de una reclamación de garantía en línea en www.intermatic.com. Esta garantía está hecha por: Intermatic Incorporated, Customer Service 1950 Innovation Way, Suite 300, Libertyville, IL 60048.

Ce manuel est également adapté pour:

Op5gy18Op5bk24Op5gy24Op2bk18Op2gy18Op2bk24 ... Afficher tout