7
Listed accessories for use with Wöhner busbar support only
All devices are suitable for use in branch and feeder circuits
CR185-C40*
CR185-C60*
Listed accessories for use with Wöhner busbar support only
All devices are suitable for use in branch and feeder circuits
Busbars
Dimension
Type No.
30x10-L*
40x10-L*
60x10-L*
80x10-L*
100x10-L*
120x10-L*
Power Terminals
Type No.
CR185-A2x300*
30x10 - 120x10
30x10 - 40x10
CR185-A80*
60x10 - 120x10
30x10 - 40x10
CR185-A2x12*
60x10 - 120x10
CR185-A80*: only for use on a system carrying maximum 1400A
CR185-A2x12*: only for use on a system carrying maximum 1520A
Connection Terminals
Type No.
(1x) CR185-C40*
(1x) CR185-C40*
(1x) CR185-C60*
(2x) CR185-C40*
(1x) CR185-C40*
(1x) CR185-C60*
(2x) CR185-C60*
CR185-C*
m m
1 0 0
SCCR
[mm]
[kA]
Current/3pole
30x10
42
1000Vac/Vdc/630A
40x10
42
1000Vac/Vdc/700A
60x10
50
1000Vac/Vdc/1100A
80x10
50
1000Vac/Vdc/1300A
100x10
50
1000Vac/Vdc/1550A
120x10
50
1000Vac/Vdc/1800A
Busbar
SCCR
[mm]
[kA]
35
1000Vac/Vdc/840A
42
1000Vac/Vdc/1400A
50
42
1000Vac/Vdc/1520A
50
5
Busbar
[mm]
30x10
40x10
60x10
80x10
100x10
120x10
Voltage/
Voltage/
Current/3pole
SCCR
Voltage/
[kA]
Current/3pole
42
1000Vac/Vdc/630A
42
1000Vac/Vdc/700A
50
1000Vac/Vdc/1100A
50
1000Vac/Vdc/1300A
50
1000Vac/Vdc/1550A
50
1000Vac/Vdc/1800A
*Type No. according to